Toshiba Tosvert RS485 Instruction Manual page 51

Rs485 communication function
Hide thumbs Also See for Tosvert RS485:
Table of Contents

Advertisement

Input terminal board status (FD06, FE06)
Input terminal board status (current status): "Communication Number FD06"
Input terminal board status (status immediately before the occurrence of a trip): "Communication
Number FE06"
Using terminal function selection parameters, functions can be assigned individually to the termi-
nals on the input terminal board.
If a terminal function selection parameter is set to 0 (no function assigned), turning on or off the cor-
responding terminal does not affect the operation of the inverter, so that you can use the terminal as
you choose.
When using a terminal as a monitoring terminal, check beforehand the function assigned to each
terminal.
Data composition of input terminal board status (FD06, FE06)
Bit
Terminal name
0
F
1
R
2
ST
3
RES
4
S1
5
S2
6
S3
7
S4
8
L1
9
L2
10
L3
11
L4
12
L5
13
L6
14
L7
15
L8
Example: Data set for FE06 when the F and S1 terminals are ON = 0011H
FE06:
Input terminal function selection 1 (f111)
Input terminal function selection 2 (f112)
Input terminal function selection 3 (f113)
Input terminal function selection 4 (f114)
Input terminal function selection 5 (f115)
Input terminal function selection 6 (f116)
Input terminal function selection 7 (f117)
Input terminal function selection 8 (f118)
Input terminal function selection 9 (f119)
Input terminal function selection 10 (f120)
Input terminal function selection 11 (f121)
Input terminal function selection 12 (f122)
Input terminal function selection 13 (f123)
Input terminal function selection 14 (f124)
Input terminal function selection 15 (f125)
Input terminal function selection 16 (f126)
BIT15
0
0
0
0
0
0
0
0
0
50
Function (parameter title)
0
0
0
0
1
0
0
9
0
E6581315
0
1
OFF
ON
bit0
0
1