Figure 5 Americas PDU for the Hitachi Universal V2B Rack (Three-phase PDU
3P30A-24C13-6C19UL.P)
Part
number
3P30A-24C
13-6C19UL.
P
APAC and EMEA single-phase PDU 1P32A-9C13-3C19CE.P
The following figure and table describe the specifications of the PDU.
Appendix E: Power distribution units for Hitachi Universal V2B Rack
Hitachi Virtual Storage Platform G900 Hardware Reference Guide
APAC and EMEA single-phase PDU 1P32A-9C13-3C19CE.P
Region
Quantity
Americas
2/rack
1/side
Power
Power input
output per
per PDU
PDU
Three phase
24 IEC C13
+ 6 IEC C19
208V 3P, 30A
sockets
(24A rated)
60Hz
Max
allowable
Delta/wYe:
current:
Delta
38.4A
NEMA L15-30P
8kVA
input power
plug
4.5 m (14.76
feet) cable
Total rack
amperage
available
38.4A (8kVA)
113