Rinnai Sensei CU199i Installation And Operation Manual page 78

Tankless water heater (commercial)
Table of Contents

Advertisement

Venturi Control
15
Ensure the Venturi motor is operating
correctly.*
Replace gas valve assembly.
Clear diagnostic code by resetting the
main power supply to the water heater.
High Outgoing Temperature
16
(safety shutdown because water heater
is too hot)
Confirm fan motor is functioning
correctly.
Replace the gas valve assembly.
Venturi Blockage
17
First, follow the recommended solutions
for Diagnostic Code 10.
If the Code 10 solutions do not correct
the problem, ensure the Venturi is not
blocked.
Please call Rinnai technical department.
Electrical Grounding
19
Check all components for electrical
short.
Data Transfer Error
21
If the PCB has been replaced, ensure
the data transfer process has been
completed.
Condensate Pump (Accessory)
25
Confirm wire connections and harness
are good.
Ensure condensate reservoir is empty
and condensate pump is operating.
Outgoing Thermistor
32
Check sensor wiring for damage.
Measure resistance of sensor.*
Clean sensor of scale build-up.
Replace sensor.
Heat Exchanger Thermistor
33
Follow the steps above for Code 32 for
troubleshooting.
Exhaust Thermistor
38
Check sensor wiring for damage.
Measure resistance of sensor.*
Replace sensor.
Freeze Protection Thermistor
41
Follow the steps above for Code 38 for
troubleshooting.
* See "Electrical Diagnostics" on Technical Data
Sheet located on inside front cover of water heater.
Rinnai Tankless Water Heater Installation and Operation Manual
Inlet Thermistor
51
Check sensor wiring for damage.
Measure resistance of sensor.*
Clean sensor of scale build-up.
Replace sensor.
Gas Valve
52
Check flame rod and wire for damage.
Check gas solenoid valve for open or
short circuit.*
Replace gas valve assembly.
Please call Rinnai technical
department
High Exhaust Gas Temperature
54
Ensure Heat Exchanger fins are clean
and not blocked.
Confirm inlet water temperature is not
too high.
Clear diagnostic code by resetting
the main power supply to the water
heater.
Combustion Fan
61
Check the motor wire harness for
loose or damaged connections.
Measure resistance of motor wire
harness.*
Ensure the combustion fan spins
freely.
Recirculation Low Flow
63
Ensure bypass plug is removed and
bypass filter is installed. (COV Mode)
Ensure both the inlet water filter and
bypass filter are clean and free of
debris.
Ensure Parameter setting are correctly
set for recirculation mode.
Ensure Pump supply voltage.
Ensure air is removed from the
recirculation line.
Water Flow Control
65
Measure resistance values of the
water flow control.*
The water flow control valve has failed
to close during the bath fill function.
Immediately turn off the water and
discontinue the bath fill function.
Contact a licensed professional to
service the appliance.
PC Board
70
Replace PC Board