Rinnai C199i Conversion Manual

Rinnai C199i Conversion Manual

Commercial condensing tankless water heaters
Hide thumbs Also See for C199i:
Table of Contents

Advertisement

Available languages

Available languages

Conversion Manual for Commercial Condensing Tankless Water Heaters
for the conversion from
Natural Gas (NG) to Liquid Propane
Gas (LPG)
for the conversion from
Liquid Propane Gas (LPG) to
Natural Gas (NG)
for adjustments at high altitude
(greater than 2000 ft / 610 m)
Refer to Adjust Gas Pressure
Settings
WARNING
This conversion kit shall be installed by a
qualified service agency in accordance with the
manufacturer's instructions and all applicable
codes and requirements of the authority having
jurisdiction. The information in these
instructions must be followed to minimize the
risk of fire or explosion or to prevent property
damage, personal injury or death. The qualified
service agency is responsible for the proper
installation of this kit. The installation is not
proper and complete until the operation of the
converted appliance is checked as specified in
the manufacturer's instructions supplied with
the kit.
C199i .................. REU-KBD3237FFUDC-US
C199e ................. REU-KB3237WDC-US
These models are NOT certified for installation in mobile homes.

Advertisement

Table of Contents
loading

Summary of Contents for Rinnai C199i

  • Page 1 Conversion Manual for Commercial Condensing Tankless Water Heaters for the conversion from C199i ....REU-KBD3237FFUDC-US  Natural Gas (NG) to Liquid Propane C199e ....REU-KB3237WDC-US Gas (LPG) These models are NOT certified for installation in mobile homes. for the conversion from ...
  • Page 2: Table Of Contents

    Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It may also be used to alert against unsafe practices. Rinnai Corporation Conversion Manual...
  • Page 3: Technical Data

    Kit Number Conversion Plate Gas Manifold (Modèle) (au gaz) (Numero de kit) Manual (Manuel (Plaque de (Gaz collecteur) de conversion) Conversion) C199i 103000055 106000067 CANNOT BE C199e 103000056 PURCHASED 100000381 C199i 103000057 SEPARATELY 106000066 C199e 103000058 Rinnai Corporation Conversion Manual...
  • Page 4: Gas Conversion Procedure

    If subsequent conversions are made NOTICE then a new conversion label must be placed on the water heater to accurately reflect the gas type. Figure 1 Ignition line, electrode and flame rod wires 10 screws attaching gas manifold Rinnai Corporation Conversion Manual...
  • Page 5: Adjust Gas Pressure Settings

    Gas Pressure Settings on the previous pages for your model, gas type, and altitude. 11. Move switch 8 of SW1 to OFF and then back to 12. Push the PC board switch B for one second. Rinnai Corporation Conversion Manual...
  • Page 6 2001-5200 ft (610-1585 m) 2.9 (74) 0.40 (10) 3.0 (76) 0.45 (11) 5201-7700 ft (1585-2277 m) 2.7 (69) 0.40 (10) 2.8 (71) 0.45 (11) 7701-10200 ft (2277-3109 m) 2.3 (58) 0.40 (10) 2.0 (51) 0.40 (10) Rinnai Corporation Conversion Manual...
  • Page 7: Check Operation

    The flame should be above the burner. clear, blue, and stable. A yellow flame is abnormal and maintenance is required. UNSATISFACTORY SATISFACTORY FRONT VIEW FRONT VIEW FLAME ROD FLAME ROD YELLOW FLAME BLUE FLAME Rinnai Corporation Conversion Manual...
  • Page 8: Operating Instructions

    1. Turn off all electric power to the appliance using 3. Locate the manual gas valve on the side of the the ON/OFF button. heater. Turn the manual valve clockwise to the full OFF position. 2. Set the thermostat to lowest setting. Rinnai Corporation Conversion Manual...
  • Page 9: Français

    Manuel de conversion pour Condenser Commercial Chauffe-eau sans réservoir pour la conversion de gaz  C199i ....REU-KBD3237FFUDC-US naturel (NG) à gaz propane C199e ....REU-KB3237WDC-US (LPG) Ces modèles NE SONT PAS certifiés pour l'installation dans les maisons mobiles. pour la conversion de gaz ...
  • Page 10 Indique une situation dangereuse potentielle, qui si elle n’est pas évitée peut amener des blessures graves ou mortelles. ATTENTION Indique une situation dangereuse potentielle, qui si elle n’est pas évitée peut amener des blessures mineures ou modérées. Peut aussi mettre en garde con- tre des pratiques dangereuses. Rinnai Corporation Conversion Manual...
  • Page 11: Procédure De Conversion Du Gaz

    étiquette de conversion doit être placée sur le chauffage de l'eau à reflètent avec précision le type de gaz. Figure 1 Allumage électrode et rod flamme lignes 10 vis qui fixent le distributeur d’alimentation en gaz Rinnai Corporation Conversion Manual...
  • Page 12: Ajustez La Pression De Gaz

    10. Calibrer la combustion « Low forcé » à l'aide du commutateur A (haut) et commutateur B (Bas). Utilisez les paramètres de pression de gaz sur les pages précédentes pour votre modèle, type de gaz et l'altitude. Rinnai Corporation Conversion Manual...
  • Page 13 2001-5200 ft (610-1585 m) 2.9 (74) 0.40 (10) 3.0 (76) 0.45 (11) 5201-7700 ft (1585-2277 m) 2.7 (69) 0.40 (10) 2.8 (71) 0.45 (11) 7701-10200 ft (2277-3109 m) 2.3 (58) 0.40 (10) 2.0 (51) 0.40 (10) Rinnai Corporation Conversion Manual...
  • Page 14: Vérifiez Fonctionnement

    Une flamme jaunâtre est anormale et requiert une intervention. SATISFAISANTE NON SATISFAISANTE VUE DE FACE VUE DE FACE FLAMME BLEUE FLAMME JAUNE TIGE DE DÉTECTION TIGE DE DÉTECTION Rinnai Corporation Conversion Manual...
  • Page 15: Instructions De Mise En Marche

    Coupez l'alimentation électrique de l'appareil en utilisant Repérez la vanne de gaz manuelle sur le côté du son bouton M/A. chauffe-eau. Fermez-la en la tournant à fond dans le sens horaire (position OFF). Réglez le thermostat sur la consigne la plus basse. Rinnai Corporation Conversion Manual...
  • Page 16 100000381 03/2015...

This manual is also suitable for:

C199e