Hisense AVW-38UCSC Installation & Maintenance Manual page 28

Inverter-driven multi-split air conditioner, heat pump
Table of Contents

Advertisement

220-240V~ 50Hz
ELB
Switch
Fuse
Power Source Cable
Pay an attention to the phase
of power source when wiring.
(5) The recommended fuse sizes etc. are
shown in Table 6.1.
(6) In the case that a conduit tube for feild-
wiring not used,fix rubber bushes with
adhesive on the panel.
G Install an ELB in the power source.
If ELB is not used, it will cause electric shock or
fire at the worst.
G The tightening torque of each screw shall be as
follows.
M4:
1.0 to 1.3 N-m
M5:
2.0 to 2.5 N-m
M6:
4.0 to 5.0 N-m
M8:
9.0 to 11.0 N-m
M10: 18.0 to 23.0 N-m
Keep the above tightening torque when wiring work.
G Install main switch and ELB for each system
separately. Select the high response type ELB that
is acted within 0.1 second.
G Separate the control wiring between outdoor unit
and indoor unit more than approximately 5 to 6cm
from power supply wiring. Do not use a coaxial
cable.
220-240V~ 50Hz
ELB
Switch
Fuse
Outdoor Unit
Control Communication Cable
Control Communication Cable
2
Shielded Twist-Pair Cable 0.75mm
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 5V)
Fig. 6.2 Wiring Connection for Indoor & Outdoor (1 PHASE)
Remote
Remote
Control Switch
Control Switch
(Option)
(Option)
No.1 Indoor Unit
NOTE:
Supply the power source of outdoor units and indoor
units respectively.
(1) Power Source Wiring
Power source wiring is fundamentally
according to this method.
(1) Power Source Wiring
Outdoor Unit Power Source
220-240V~ 50Hz
1
ELB
2
FUSE
3 S
4
Outdoor
Unit
5
20
No.2 Indoor Unit
Remote Control
Switch Cable
2
Shielded Twist-Pair Cable 0.75mm
x 2
This cable dose not need any polarity.
Do not apply an excessively high
voltage to this cable. (Rated Voltage: 12V)
ELB (Earth Leakage Breaker)
1
FUSE
2
3
S (Main Switch)
Power Source Wiring (O.U.)
4
5
Earth Wiring (O.U.)
Transmission Wiring (O.U. ~ I.U.)
6
7
Power Source Wiring (I.U.)
8
Earth Wiring (I.U.)
Indoor Unit Side
6
7
S
FUSE
Indoor
Unit
ELB
Indoor Unit
Power Source
220-240V~ 50Hz
7
7
Indoor
Unit
8
8
6
6