Fluke DSX-CHA-5-IX-S User Manual page 4

Ix industrial adapters for industrial ethernet
Table of Contents

Advertisement

Test and Certify a Channel
1
On the home screen, tap the test setup panel.
2
On the CHANGE TEST screen, tap NEW TEST.
3
On the TEST SETUP screen, tap the panels to select settings:
Cable Type: If the correct type is not in the LAST USED list, tap
MORE, tap Manufacturers, tap the correct manufacturer, then tap
a cable type.
Shield Test: Shows only for shielded cable types. To get a FAIL
result if the shield is open, select On. See the Versiv Series Users
Manual for more information.
Test Limit: If the correct limit is not in the LAST USED list, tap
MORE, then tap a group.
Outlet Configuration: Select IX Chan.
4
On the TEST SETUP screen, tap SAVE when your test setup is
completed.
5
Connect the testers to the link, as shown in Figure 2 or 3.
6
Tap TEST on the main tester or press
tester.
4
on the main or remote
B