Parameter
Definition
DISABLE U>
Provides ability to enable/disable the
(10 min)
parameter
"SET U>(10 min)"
Disable U<
Provides ability to enable/disable the In-
termediate Under Voltage Set point U<
Disable F>
Provides ability to enable/disable the In-
termediate Over Frequency Set point F>
Disable F<
Provides ability to enable/disable the In-
termediate Under Frequency Set point F<
U>(10 min)
Provides ability to limit the power for 10
Der.
minutes due to the high average voltage
value set by the parameter "SET U>(10
min)"
Slow Ramp
Provides ability to slowly ramp the Output
Power at connection( Soft start)
OF Derating
Provides ability to limit the Output Power
due to the high grid frequency
Reset Country
Provides ability to reset the country code
S
New PW - Used to change the password for accessing the SETTINGS menu. The default
password is 0000 and can be changed using the display keyboard.
Use ENTER to scroll the digits (from left to right)
Use ESC to return to the previous digit (from right to left)
Press ESC several times to return to the previous menus
Use DOWN to progressively scroll the numerical scale downwards (from 9 to 0)
Be careful to memorize the new password. For security purposes there is no reset function.
If the password is misplaced it will not be possible to access the inverter.
Cash - Used to set the name of the currency and the value given to 1 kWh of energy
produced. The correct setting of these parameters displays the actual earning/saving given
by the system.
Name: the chosen value is set (default is $, USD).
Val/KWh: indicates the cost/incentive of 1 KWh expressed in the chosen currency (default
is 0.16).
Time – Used to set the current date and time (daylight saving time not included).
Language – Used to set the menu language.
Vstart – Used to set the Vstart voltage (separately for both channels if they are configured in
independent mode). Change the activation voltage only if necessary. A configuration program
that can help to correctly size the photovoltaic system is available on the website.
Default
Value
Disable
Enable
Enable
Enable
Disable
Disable
Disable
Not Appli-
cable
- 42 -
4 - Operations
Adjustable
Ranges
Disable or En-
able
Disable or En-
able
Disable or En-
able
Disable or En-
able
Disable or En-
able
Disable or En-
able
Disable or En-
able
Not Applicable