Parameter
Definition
SET U>>
Indicates the value of the absolute over
voltage set point beyond which the in-
verter disconnects from the grid. [120%
of Nominal line to neutral Voltage]
SET U<<
Indicates the value of the absolute under
voltage set point below which the inverter
disconnects from the grid [50% of Nomi-
nal line to neutral Voltage]
SET F>>
Indicates the value of the absolute over
frequency set point beyond which the
inverter disconnects from the grid
SET F<<
Indicates the value of the absolute un-
der frequency set point below which the
inverter disconnects from the grid
SET U>
Indicates the value of the intermediate
over voltage set point beyond which the
inverter disconnects from the grid [110%
of Nominal line to neutral Voltage]
SET U>(10
Inverter disconnects from the grid after 10
min)
minutes in case the average grid voltage
overcomes the threshold value(305V)
SET U<
Indicates the value of the intermediate
under voltage set point below which the
inverter disconnects from the grid [88% of
Nominal line to neutral Voltage]
SET F>
Indicates the value of the intermediate
over frequency set point beyond which
the inverter disconnects from the grid
SET F<
Indicates the value of the intermediate un-
der frequency set point below which the
inverter disconnects from the grid
SET U Conn> Indicates the value of the intermediate
over voltage (line to neutral) set point to
allow the inverter to connect to the grid for
the first time.
SET U conn<
Indicates the value of the intermediate
under voltage (line to neutral) set point to
allow the inverter to connect to the grid for
the first time.
SET F conn>
Indicates the value of the intermediate
over frequency set point to allow the
inverter to connect to the grid for the first
time.
Default
Value
120% of
Nominal line
to neutral
Voltage
50% of
Nominal line
to neutral
Voltage]
60.5 Hz
57 Hz
110% of
Nominal line
to neutral
Voltage
110% of
Nominal line
to neutral
Voltage]
88% of
Nominal line
to neutral
Voltage]
60.5 Hz
59.3 Hz
110% of
Nominal line
to neutral
Voltage]
88% of
Nominal line
to neutral
Voltage
60.5 Hz
- 40 -
4 - Operations
Adjustable
Ranges
Fixed
Fixed
Fixed
Fixed
Fixed
(110% x V
) to
LN
(115% x V
)
LN
Fixed
60.2 Hz to
63.0 Hz
59.8 Hz to
57 Hz
(110% x V
) to
LN
(115% x V
)
LN
(50% x V
) to
LN
(88% x V
)
LN
60.2 Hz to
63.0 Hz