LEGRAND Wattstopper LMSW-610-S Installation Instructions Manual page 5

Dlm wireless slim switches with ipv6/bluetooth(r) low energy technology
Table of Contents

Advertisement

5. Exit PtP mode. From any device, press the Config button 3 times. After a few seconds, the LED on each Room controller, switch
or sensor currently in PtP mode will flash either white or a red/green/blue sequence and reboot, leaving the default network and
migrating to the new network. Then, the LED on the room controller will flash blue and the pairing process finishes. The default
Network ID on all devices will change to a new number, based on the last four digits of the Mac address on the primary room
controller, and now those devices will communicate only with each other and not any devices which have not been paired.
NOTE: It is important to exit PtP mode within the three minute time limit mentioned above. If you do not, none of the device
pairings will be remembered and you have to start the process over from the beginning.
Pairing a device to an existing network
If you need to add the LMSW-6xx-S to an existing in room network, follow the procedure below:
1. Enter wireless Push-to-Pair (PtP) mode on the room controller or any currently paired battery device. Press the Config
button three times (within three seconds).The LED on the room controller and any paired battery devices that are currently awake
will flash green.
2. Enter PtP mode on the LMSW-6xx-S. Press the Configuration button three times. As with the room controller, the LED on the
switch will flash green.
3. Pair the devices. Press the Config button on the LMSW-6xx-S one more time to pair the LMSW-6xx-S to the room controller.
The load connected to the room controller will toggle once (if the load is OFF, it will turn ON; if ON, it will turn OFF) to indicate that
pairing was successful and its config LED will turn solid green.
4. Exit PtP mode. From any device, press the Config button 3 times. After a few seconds, the LED on the LMSW-6xx-S will flash a
red/green/blue sequence and reboot, leaving the default network and migrating to the new network. Then the LED on the room
controller will flash blue while it completes the pairing process. The Network ID of the LMSW-6xx-S will change to the value used
by the previously paired devices and the room controller also returns to that value.
Push-to-Pair in a Room with Wired Room Controllers via an LMBC-650
NOTE: Once you enter PtP mode on the LMBC-650 wireless bridge, a three minute timer begins. If the Config button on any wireless
device in the room is pressed, the timer resets and begins the three minute countdown again. If no Config button is pressed
within three minutes, the LMBC-650 will exit PtP mode.
1. Enter PtP mode on the LMBC-650. Using a pointed tool, press the Config button three times (within three seconds) until the LED
on the LMBC-650 flashes green.
2. Enter PtP mode on the LMSW-6xx-S. Press the Config button (right side of Legrand badge) three times. As with the wireless
bridge, the LED on the switch will flash green.
3. Pair the LMSW-6xx-S. Press the Config button on the LMSW-6xx-S one more time to pair it to the LMBC-650. Loads connected
to the LMBC-650 will toggle once (if the load is OFF, it will turn ON; if ON, it will turn OFF) to indicate that pairing was successful.
Also, the LMSW-6xx-S's blinking LED will turn to solid green as another indicator of a successful pairing.
NOTE: If there are any wireless sensors, dimmers, or additional switches in the room, repeat steps 2 and 3 for each of those
devices so that all devices are paired together in the same network. For each device, loads will toggle during step 3 and its
config LED will turn solid green.
4. Exit PtP mode. From any wireless device, press the Config button 3 times. After a few seconds, the LED on each switch, sensor,
and wireless bridge currently in PtP mode will flash white or a red-green-blue sequence and reboot, leaving the default network
and migrating to the new network. Then, the LED on the LMBC-650 will flash blue and the pairing process finishes. The default
Network ID on all devices will change to a new number, based on the last four digits of the Mac address on the LMBC-650, and
now those devices will communicate only with each other and not any devices which have not been paired.
NOTE: It is important to exit PtP mode within the three minute time limit mentioned above. If you do not, none of the device
pairings will be remembered and you have to start the process over from the beginning.
NOTE: Hybrid rooms do not support automatic binding via PnG. The configuration button on any wireless device may be pressed once
to toggle connected loads to verify communication and operation. Programming must be performed via LMCS-100.
DEVICE PAIRING AND UNIT ADJUSTMENT USING THE DLM CONFIG APP
The DLM Config App is available for both iOS
your device to download.
The app provides the ability to pair various devices in a room. Additionally, you can modify load
binding and edit various DLM parameters for each device.
For details on the features and operation, download the DLM Config App User Guide from the Wattstopper web site at :
https://www.legrand.us/wattstopper.aspx
NOTE: LMCS-100 software, version 5.3 or later can also be used to pair devices and edit DLM parameters. However, LMCS-100
requires use of an LMBR-650.
®