Generac Power Systems EcoGen 15kW Installation Manuallines page 52

60 hz air-cooled generators
Hide thumbs Also See for EcoGen 15kW:
Table of Contents

Advertisement

Quick Reference Guide
Active Alarm
LED
OVERVOLTAGE
RED
AUXILIARY
RED
SHUTDOWN
LOW BATTERY
YELLOW
BATTERY
YELLOW
PROBLEM
CHARGER
YELLOW
WARNING
CHARGER
YELLOW
MISSING AC
SERVICE A
YELLOW
SERVICE B
YELLOW
INSPECT BATTERY
YELLOW
48
Problem
Unit will not start in
Check LED's / Screen
AUTO with utility loss.
Unit will not start.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Yellow LED illuminated in
any state.
additional information.
Action
Contact an IASD.
for alarms.
Check auxiliary
Set auxiliary shutdown switch(es) to
shutdown switch(es).
CLOSED (I).
Clear alarm. Using control panel, check
battery by navigating to BATTERY MENU
Check screen for
option from MAIN MENU. If battery
condition displays GOOD, contact an IASD.
If control panel displays CHECK BATTERY,
replace battery.
Check screen for
Contact an IASD.
Check screen for
Contact an IASD.
Check screen for
Contact an IASD.
Check screen for
Perform SERVICE A maintenance. Press
ENTER to clear.
Check screen for
Perform SERVICE B maintenance. Press
ENTER to clear.
Check screen for
Inspect battery. Press ENTER to clear.
Installation Guidelines For 60 Hz EcoGen™ Generators
Solution

Advertisement

Table of Contents
loading

Table of Contents