Fuel Consumption; Fuel Line Sizing - Generac Power Systems EcoGen 15kW Installation Manuallines

60 hz air-cooled generators
Hide thumbs Also See for EcoGen 15kW:
Table of Contents

Advertisement

Fuel Conversion / Gas Connections

Fuel Consumption

Generator
15 kW
3
* Natural gas is in m
/h / ft
** Propane is in gal/h (LP) / L/h (LP) / ft
*** Values given are approximate
These are approximate values. Use the appropriate spec sheet or fuel data decal for specific values.
Verify gas meter is capable of providing enough fuel flow to include household appliances and all other loads.
NOTE: The fuel supply and pipe MUST be sized at 100% load BTU/h (Megajoule/h) rating.
Always see fuel data label for the correct BTU/h or Megajoule/h, and required fuel pressures:
– Natural Gas:
BTU/h = ft
Megajoules/h = m
– Liquid Propane Gas (Vapor):
BTU/h = ft
Megajoules/h = m

Fuel Line Sizing

Selecting the correct size fuel line is crucial to correct
operation of the unit.
IMPORTANT NOTE: Generator inlet size DOES NOT
dictate the size of gas pipe to be used!
For further information see NFPA 54 for NG, or NFPA 58
or ICC IFGC for LP.
Measure distance from generator to fuel source.
IMPORTANT NOTE: Generator should be plumbed
directly from the fuel source through an appropri-
ately sized and correctly placed fuel pressure regula-
tor, not off the end of an existing low pressure
system.
22
Natural Gas
1/2 Load
Full Load
5.52 / 195
7.87 / 278
3
/h
3
/h (LPV)
3
/h x 1000
3
/h x 37.26
3
/h x 2500
3
/h x 93.15
Propane
1/2 Load
1.84 / 6.95 / 66.8
Installation Guidelines For 60 Hz EcoGen™ Generators
Full Load
2.76 / 10.45 / 100