LP Gas (Vapor) Installation (Typical)
LPG BTU/h = ft
A
Fuel data decal
B
Minimum distance from rear obstruction—see
C
Manual fuel shutoff valve (pressure port optional)
Must be located no more than 6 ft (1.83 m) away from fuel inlet.
D
Pipe fittings (field supplied)
E
Flexible fuel line
F
Verify minimum distance requirements for regulator vent according to local gas codes. Regu-
lator should be a minimum of 5 ft (1.5 m) from generator. Local codes and regulator manu-
facturer may have further clearance requirements.
G
Clamp
H
Secondary fuel pressure regulator
J
Manual shutoff valve
K
Primary fuel pressure regulator
L
Fuel tank—sized large enough to provide required MJ/BTU for generator operating at FULL
load and ALL connected appliance loads. Be sure to correct for weather evaporation.
Installation Guidelines For 60 Hz EcoGen™ Generators
A
D
E
G
C
B
3
/h X 2500
Figure 5-7. LP Gas (Vapor) Installation (typical)
H
F
Megajoules/h = m
Distance Requirements
Fuel Conversion / Gas Connections
J
K
L
3
/h X 93.15
008966