6.5
Servomotor adjustment
SQM 40 servomotor provides simultaneous adjustment of the air
damper by means of the variable profile cam and the gas butterfly
valve.
It performs a 130° rotation in 45 s.
It is equipped with three adjustable cams that activate as many
contacts, factory set as follows:
RED cam
I
Limits rotation toward maximum position.
BLUE cam
Limits rotation toward minimum position.
II
With burner off, the air damper must be
closed.
ORANGE cam:
III
Adjusts the ignition position and the MIN
output.
IV Not used
V Not used
VI Not used
Each cam is equipped with a screw that adjusts the activation
point of contacts.
20159111
Start-up, calibration and operation of the burner
130°
0°
20°
20074577
28
GB
Fig. 25