Carrier AquaEdge 23XRV Start-Up, Operation And Maintenance Instructions Manual page 40

High-efficiency variable speed screw chiller with greenspeed intelligence and pic6 controls
Table of Contents

Advertisement

COOLER
FRAME SIZE
LENGTH
FT (M)
12
(3.6)
3
14
(4.3)
12
(3.6)
4
14
(4.3)
12
(3.6)
5
14
(4.3)
FRAME SIZE
A1
A2
A3
A4
A5
A6
B1
B2
B3
B4
B5
B6
CHILLER SHIPPED WITH HOLDING CHARGE
If the chiller has been shipped with a holding charge, the refriger-
ant is added through the refrigerant charging valve (Fig. 27-30,
valves 1a and 1b) or to the pumpout charging connection. First
evacuate the nitrogen holding charge from the chiller vessels.
Charge the refrigerant as a gas until the system pressure exceeds
35 psig (141 kPa) for R-134a or 39 psig (268 kPa) for R-513A.
After the chiller is beyond this pressure the refrigerant should be
charged as a liquid until all the recommended refrigerant charge
has been added. Ensure that pumps are running while system is
being charged.
TRIMMING REFRIGERANT CHARGE
The 23XRV chiller is shipped with the correct charge for the de-
sign duty of the chiller. The Evaporator Approach (difference be-
tween Saturated Refrigerant Temp and Leaving Water Temp) can
be checked against the design conditions to confirm that the
charge is correct. In the case where leaks have been found and cor-
rected and the Evaporator Approach is greater than about 4°F
(2.2°C) above design, add refrigerant until the full load design
LTD is approached. (A high Evaporator Approach can also be
caused by dirty tubes, water box division plate bypass, a partially
closed liquid isolation valve, or the float valve.)
Table 10 — Refrigerant Charges, Frame Sizes 3-5
COOLER CODE
lb (± 25 lb)
30
31
32
35
36
37
40
41
42
45
46
47
50
51
52
55
56
57
Table 11 — Refrigerant Charges, Frame Sizes A,B
COOLER LENGTH
FT (M)
lb (± 25 lb)
12
(3.6)
14
(4.3)
CHARGE AMOUNT (R-134a, R-513A)
WITH ECONOMIZER
kg (± 11 kg)
800
363
800
363
800
363
910
413
910
413
910
413
900
408
900
408
900
408
1015
460
1015
460
1015
460
1250
567
1250
567
1250
567
1430
649
1430
649
1430
649
CHARGE AMOUNT (R-134a, R-513A)
WITH ECONOMIZER
kg (± 11 kg)
840
381
860
390
880
399
900
408
930
422
960
435
950
431
970
440
1000
454
1020
463
1060
481
1090
494
Trimming the charge can best be accomplished when the de-
sign load is available. The calibration of the Evaporator Refrig-
erant Pressure and Leaving Chilled Water Temp should be
confirmed prior to checking for proper Evaporator Approach.
Compare the difference between Evaporator Refrigerant Temp
and Leaving Chilled Water Temp to the chiller design condi-
tions. Add or remove refrigerant, if necessary, to bring the
cooler leaving temperature difference to design conditions or
within minimum differential.
Check for low load oil recovery after making adjustments to the
refrigerant charge. The bubbling mixture of refrigerant and oil
mixture should be visible through the vaporizer sight glass at low
load when the oil reclaim valve is open. If a bubbling mixture is
not observed when the oil reclaim valve is open, add refrigerant.
The preferred location at which refrigerant should be added di-
rectly into the chiller is through the service valves on top of the
cooler or condenser. If these valves are not accessible due to
presence of an attached pumpdown unit which does not have a
storage tank, slowly add charge through the valve connected to
the side of the condenser drain float sump. Adding charge
through the cooler refrigerant pumpout valve at the base of the
cooler (off the liquid line) may force debris into the condenser
float valve and is not recommended.
40
WITHOUT ECONOMIZER
lb (± 25 lb)
kg (± 11 kg)
650
295
650
295
650
295
760
345
760
345
760
345
750
340
750
340
750
340
865
392
865
392
865
392
1100
499
1100
499
1100
499
1280
581
1280
581
1280
581
WITHOUT ECONOMIZER
lb (± 25 lb)
kg (± 11 kg)
820
372
840
381
860
390
880
399
910
413
940
426
930
422
950
431
980
445
1000
454
1040
472
1070
485