13 FAQ
Q1. How many types of communication ports does the Logger4000 support, what are
the corresponding ports, and how to set the port parameters?
T T y y p p e e
Ethernet
RS485
PLC
Q2. What are the forwarding protocols supported by the Logger4000?
P P r r o o t t o o c c o o l l
ModbusRTU/ModbusTCP
IEC104
P P a a r r a a m m e e t t e e r r s s e e t t t t i i n n g g
P P o o r r t t
Default IP: 12.12.12.12; subnet mask: 255.255.255.0
Gateway: 12.12.12.1
FE1~FE4
DNS1: 1.2.4.8
DNS2: 8.8.8.8
Default Baud rate: 9600
Check bit: Null
A1B1~A7B7
Data bit: 8
Stop bit: 1
Default Baud rate: 115200
Check bit: Null
L1,L2,L3
Data bit: 8
Stop bit: 1
D D e e s s c c r r i i p p t t i i o o n n
The Logger4000 sends the collected data of devices (-
such as inverter, combiner box, Meteo Station) to the
background. The background allocates forwarding
addresses to theses devices, thereby accessing and
obtaining the data of the devices.
1. Add or search devices on the Web interface (such
as inverter, combiner box, Meteo Station).
2. Export the IEC104 point table by clicking "Settings"
-> "IEC104 service settings". The point table shows
measuring point information of devices.
85