TAS APFC-06 04 User Manual page 33

Table of Contents

Advertisement

Power Factor Controller APFC 06
EDIT PARAMETERS : MINIMUM , MAXIMUM AND DEFAULT VALUES
PARAMETER
GENERAL and IO
1] Password (Enable: 1/ Disable: 0)
2] Change Password
3] Load Default (Yes: 1/ No: 0)
4] THD to display
(F-THD: 1/R-THD: 0)
5] Unit ID
(0000)
6]Aux I/P FUNCTION
(None ; 0 , O/P En Di : 1, Reset Bank Flt : 2 )
7]Aux O/P FUNCTION (None : 0 , Trip Flt : 1 ,
Sys Flt : 2 , Out Of Bank : 3 )
SYSTEM
1] Meas. Voltage
1] Meas. Voltage
2] EXT-PT ratio
3] Current CT primary (Mains)
4] PF Upper limit: Mains
( [ Ind: 1/ Cap: 0 ] ,
5] PF Upper Limit: Mains
( Ind: 1/ Cap: 0 [ 0.999 ] )
6] PF Low limit: Mains
( [ Ind: 1/ Cap: 0 ] ,
7] PF Low Limit: Mains
( Ind: 1/ Cap: 0 [ 0.970 ] )
8] Measurement Supply (Voltage Feedback)
Frequency: 50 or 60 Hz
0: 50 Hz, 1: 60 Hz
9] CT Polarity Check
(0: Disabled & 1: Enabled)
0.999 )
0.970 )
MIN
MAX
0
1
0000
9999
0
1
0
1
0000
9999
None
Reset Bank
flt
Out of
None
Banks
110
480
0000.1
5999.0
6500
1
0
1
0.100
0.999
0
1
0.100
0.999
0
1
0
1
- 31 -
INCREMENT /
FACTORY
DECREMENT
DEFAULT
STEP SIZE
1
1
1
0001
1
0
1
1
1
0000
-
None
-
None
1
415
1
0001.0:1
1
1000
1
[Ind: 1]
0.001
[0.980]
1
[Ind: 1]
0.001
[0.970]
1
50 Hz
1
Disabled