TAS APFC-06 04 User Manual page 28

Table of Contents

Advertisement

Power Factor Controller APFC 06
• C Series: Various control series (C Series) can be selected
00: 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1.
01: 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2.
02: 1 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3.
03: 1 2 3 4 4 4 4 4 4 4 4 4 4 4 4 4.
04: 1 2 4 4 4 4 4 4 4 4 4 4 4 4 4 4.
05: 1 2 3 6 6 6 6 6 6 6 6 6 6 6 6 6.
06: 1 2 4 8 8 8 8 8 8 8 8 8 8 8 8 8.
07: 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2.
08: 1 1 1 1 1 6 6 6 6 6 6 6 6 6 6 6.
09: 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2.
• E-Series: As explained earlier, this series is the user defined series.
Digits can be adjusted from 1 to F i.e., 1 to 15.
• Unequal Bank kVAr [1....12]: If unequal kVAr bank configuration is
used, these parameters are to be defined for every bank kVAr (at defined
Capacitor Bank Voltage). APFC 06 has a in built intelligent algorithm to
select the best possible combination to suit the exact kVAr
requirement
for compensation.