Probe Information - Foster ECORPO G3 EP700H Service Manual

Table of Contents

Advertisement

Probe Information

The probe is a type 10k NTC. The probes are identical in characteristics with the T1 and T2 identification markings and different colours being for
ease of identification and not for functional reasons. Please refer to the image below for probe identification.
Probe Indentification
Tx
1 - Air probe
Probe manufacturer
2 - Evaporator probe
3 - Condenser probe
Probe Resistance
NTC10K Temperature Resistance Table
TEMP. (°C)
R-low (KW)
-30
109.522
-25
84.823
-20
66.27
-15
52.229
-10
41.477
-5
33.147
0
26.678
5
21.63
10
17.643
15
14.472
20
11.938
25
9.9
30
8.217
35
6.854
40
5.745
16
LAEx
x-xx
Manufacture
Month - Year
SN4K
R-mid (KW)
R-high (KW)
113.347
117.294
87.559
90.374
68.237
70.255
53.65
55.104
42.506
43.557
33.892
34.651
27.219
27.767
22.021
22.417
17.926
18.21
14.674
14.877
12.081
12.224
10
10.1
8.315
8.413
6.948
7.043
5.834
5.923
Sx xK xx Px
N - NTC
1 - 1KΩ
Length in decimeters
T - PTC
2 - 2kΩ
15 = 1.5m
4 - 10kΩ
20 = 2m
35 = 3.5m
P1 - Probe 1
P2 - Probe 2
P3 - Probe 3
www.fosterrefrigerator.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents