Other Information

Alarms/Warnings:
During operation the current temperature inside the appliance will be displayed. At certain times this will change to indicate a particular appliance
operation or fault. The indicators you may see are as follows:
The temperature alarms are either relative to the set point or an absolute value. This is controlled by the value of parameter 'ATM' . Where the alarms
are relative the low alarm is the set point minus parameter 'ALR' and the high alarm is the set point plus 'AHR' . When the temperature has been
outside this value for the value of 'ATD' the relevant indicator will be displayed.
hi - The internal temperature of the appliance is higher than described above. Ensure that the door is closed and that the air flow inside is not
obstructed by excesive or poor loading of product. The alarm will reset if the temperature falls to a normal level. If this does not happen please
contact your authorised dealer or Foster Service.
Lo - The internal temperature of the appliance is lower than described above. Check to ensure that the appliance has not been loaded with
product at a lower temperature than the normal appliance operating temperature. If this is not the case please call your authorised dealer or Foster
Service.
dO - The appliance door is open. Close the door to cancel the alarm. Note - the door switch is a magnetic switch located in the bottom edge
of the front cover. If the cover is hinged up or removed for access purposes the door switch will not function and the door open alarm will be
displayed.
tA - Air probe has failed.. Call your authorised dealer or Foster Service to arrange for this to be replaced. During this time the appliance cannot
maintain an accurate temperature and all product should be removed and the appliance switched off.
tE - Evaporator probe has failed (not applicable to all models). Call your authorised dealer of Foster Service to arrange for this to be replaced.
PF - The mains power has been removed from the appliance for a period of time and has now been restored. This may have resulted in a rise in
appliance temperature. Caution should be taken when using products stored within to ascertain whether these products are suitable for use. Upon
restoration of the power supply the appliance will resume normal operation and the PF can be cancelled by pressing button 3 once.
HC - The condenser temperature is higher than it should be. If the appliance is being subjected to particularly high ambient temperatures steps
should be taken to reduce this. If the ambient temperature is not high or reducing the temperature does not rectify the fault please contact your
authorised dealer or Foster Service.
Cnd - The condenser clean period has expired. Please contact your authorised dealer or Foster Service.
While in an alarm condition icon 5 will also be illuminated.
(Some indications are only visible periodically during specific appliance operations such as defrost or when activated through use of the appliance).
G3 Cabinets - Service Manual
15