Safe Use Instructions — Emerson FB3000 RTU
Part D301876X012
August 2019
For more information on grounding or if your installation
uses cathodic protection, refer to
Equipment Installation, Grounding, and Wiring
(D301452X012).
Wiring to Power
Wire the FB3000 through the bottom of the chassis.
The terminal blocks accept wiring 2mm in diameter
(12 AWG) or smaller. To connect the wire to the
removable block compression terminals:
Bare the end (6mm maximum) of the wire.
Insert the bared end of the wire into the clamp
beneath the termination screw.
Tighten the screw.
Expose a minimum of bare wire to prevent short circuits.
Allow some slack when making connections to prevent
strain.
Connect the power wiring. Review the power wiring
descriptions in Chapter 2 of the
Instruction Manual
(part D301851X012).
Verify the hook-up polarity is correct.
To make DC power supply connections:
Remove the terminal block connector from the
socket.
Insert each bare wire end into its appropriate
connector and secure the wire (see
Plug the terminal block connector back into the
socket.
1
Input power from external power supply
(power for RTU)
2
Loop power from external power supply
(power for field devices)
Figure 9. Wiring to DC Power Supply
Wiring to Communications & I/O
Connect the wiring to the terminal blocks on the I/O and
communications modules. Refer to Chapter 2 and
Chapter 3 in the
Emerson FB3000 RTU Instruction Manual
(part D301851X012) or the
Start Guide
(part D301859X012) for wiring schematics
and explanations.
4
Site Considerations for
Emerson FB3000 RTU
Figure
9).
Emerson FB3000 RTU Quick
Powering Up the FB3000
DANGER
Do not attempt to connect power or disconnect power
from the unit in a hazardous area. Ensure the area is
non-hazardous. Failure to do so could result in an
explosion.
To start up the FB3000, apply power by plugging in the
terminal block for the power supply module.
Periodically inspect the wiring for signs of
deterioration.
Configuring the FB3000
You must install Emerson's Field Tools configuration
software (which includes FBxConnect™) on your PC to
configure the FB3000 for use. Refer to the Emerson
FB3000 RTU Quick Start Guide
instructions on installing and using this software.
Resetting the FB3000
If you are experiencing problems that appear to be
software related, try resetting the FB3000. Refer to the
Service and Troubleshooting
FB3000 RTU Instruction Manual
for specific instructions.
Note: You lose all configuration and log data with a
reset. If possible, make a backup of
configuration and log data before attempting
any type of reset.
Replacing Parts in the FB3000
Refer to
Table 1
for a list of user-serviceable parts and their
respective field replacement guides.
Returning the FB3000
If you are experiencing problems that appear to be
hardware-related, verify the wiring. If you still experience
problems, contact your local sales office for return
authorization. To return the device:
1. Back up all configuration and data before removing
the device from process. Then remove power from
the device and remove all external wiring.
2. Uninstall the device.
3. Place the device into a box safe for shipping or
storage.