POWER
Operating Range:
Field Supply: 5A at 10.5Vdc to 30Vdc
Controller Supply: 5A at 10.5Vdc to 30Vdc
ENVIRONMENTAL
Operating Temperature:
Increased Safety (Ex ec): —40 C to +75 C
Storage Temp.: —40 C to +85 C
Operating Humidity: 5-95% non-condensing per IEC 68-2-
3.
WEIGHT
1.65 kg (3.675 lbs) (for housing, backplane, and CPU)
APPROVALS
Evaluated to the following European Standards (EMC):
Emissions
EN 55011:2009+A1:2010
EN 55032:2012
Immunity
EN 61326-1
EN 61000-4-2:2009 (Electrostatic Discharge)
EN 61000-4-3:2006+A1:2008+A2:2010 (Radiated EMC
Field)
EN 61000-4-4:2012 (Fast Transients/Burst)
EN 61000-4-5:2006 (Surges)
EN 61000-4-6:2009 (Conducted RF)
EN 61000-4-8:2010 (Power Frequency Magnetic Field)
EN 61000-4-11:2004 (Voltage Dips/Interruptions)
Evaluated to the following Approval Standards:
EN 60079-0:2012+A11:2013
EN 60079-7:2015
Evaluated to the following Standards (IEC):
th
IEC 60079-0 (2011), 6
Edition
IEC 60079-7 (2017), 5.1 Edition
Product Markings for Hazardous Locations:
Ex ec IIC T4 Gc (Tamb = —40 C to +75 C)
II 3 G
SIRA 19ATEX3013X
IECEx CSA 19.0003X
DANGER
When installing units in a hazardous area, make sure all
installation components selected are labeled for use in
such areas. Installation and maintenance must be
performed only when the area is known to be non-
hazardous. Installation or maintenance in a hazardous
area could result in personal injury or property damage.
Always turn off the power to the FB3000 before you
attempt any type of wiring. Wiring of powered
equipment could result in personal injury or property
damage.
2
To avoid circuit damage when working inside the unit, use
appropriate electrostatic discharge precautions, such as
wearing a grounded wrist strap.
Check the input power polarity before connecting power
to the FB3000. Wiring of powered equipment could result
in personal injury or property damage.
The following tools are required for installation,
maintenance, and troubleshooting:
Personal computer running Microsoft
Professional or Windows 8.1 Pro or Windows 10 Pro
and Emerson Field Tools configuration software
(providing FBxConnect™).
#1 and #2 Phillips (cross-head) screwdriver.
3 mm (1/8-inch) flat-head screwdriver.
Unpacking
You receive the FB3000 in a box. Remove it from the box.
Examine the packing list carefully to ensure you have all
components.

Installation

1. Find a suitable location for the FB3000. When
selecting an installation site, be sure to check all
clearances.
Figure 3. Front View of the FB3000