Annex; Technical Data; Interfaces; Electrical Data - JUMO 705043 Installation Instructions Manual

Router module 1-port
Table of Contents

Advertisement

Available languages

Available languages

4

Annex

4.1

Technical data

4.1.1

Interfaces

System bus (input, front side)
Designation
Type
Number
Connecting cable
Application
System bus (output, lateral)
Designation
Type
Number
Application
4.1.2

Electrical data

Voltage supply
Symbol (see nameplate)
Connection
Voltage
Residual ripple
Current consumption
Power consumption
Conductor cross section on terminals GND
and +24 V
Wire or stranded wire without ferrule
Stranded wire with ferrule
2 × stranded wire with twin ferrule
with plastic collar
Stripping length on terminals GND and +24 V 10 mm
Electrical safety
Protection rating
Electromagnetic compatibility
Interference emission
Interference immunity
Bus In
RJ45
1
Network cable (patch or crossover cable), at least CAT5 (S/FTP)
Connection to a central processing unit 705003 or a router module
(705041, 705042)
None (side plug connector)
System specific
1
Connection to an input/output module
At the front (removable terminal strip, 2-pole with PUSH IN technolo-
gy)
DC 24 V +25/-20 % SELV
5 %
30 mA (at DC 19.2 V)
Current consumption of lined-up modules also has to be considered!
0.6 W
2
Min. 1.5 mm
, max. 2.5 mm
2
Min. 1.5 mm
, max. 2.5 mm
2
1.5 mm
According to DIN EN 61010-1
Overvoltage category III, pollution degree 2
III
Acc. to DIN EN 61326-1
Class A – only for industrial use –
Industrial requirement
2
2