3 Electrical connection
3.2

Galvanic isolation

(1) Functional galvanic isolation for connection of SELV or PELV electrical circuits.
3.3

Connection diagram

CAUTION!
At maximum load, the temperature may exceed 60 °C at the terminals.
As a result the insulation of the cable may be damaged.
 The cable must be heat resistant up to at least 80 °C.
CAUTION!
The maximum current carrying capacity of the side connector (DC Out) for the voltage supply of
the connected modules is 8 A.
If this current is exceeded, the entire system may be damaged.
 Add up the current consumption of all connected modules (see their technical data). If necessary,
distribute modules on several DIN rails and, if necessary, also power supply units.
NOTE!
Only copper conductors are allowed to be connected to the terminals.
18
System bus In
Voltage supply In
(at the front)
(1)
Side
system bus Out
Voltage supply Out