Density; Viscosity; Pressure Shocks; Pressure Tightness - Endress+Hauser Liquiphant FTL62 Operating Instructions Manual

Vibronic point level switch with highly corrosion-resistant coating for liquids
Hide thumbs Also See for Liquiphant FTL62:
Table of Contents

Advertisement

Technical data
58
The device function is limited during the pressure test.
The mechanical integrity is guaranteed at pressures up to 1.5 times the process nominal
pressure PN.
14.4.5

Density

Liquids with density > 0.7 g/cm
Switch position >  0.7 g/cm
Liquids with density 0.5 g/cm
Switch position >  0.5 g/cm
Liquids with density >  0.4 g/cm
• Optionally available, not suitable for SIL applications
• Fixed value that cannot be edited
The function of the DIP switch is interrupted
For distinguishing between media/density detection, use the Liquiphant Density
(FEL60D) with a density computer.
14.4.6

Viscosity

≤ 10 000 mPa⋅s
14.4.7

Pressure shocks

≤20 bar/s (290 psi/s)
14.4.8

Pressure tightness

Up to vacuum
In vacuum evaporation plants, select the 0.4 g/cm
14.4.9

Solids contents

⌀ ≤ 5 mm (0.2 in)
14.5

Additional technical data

Technical Documentation TI01539F.
3
3
(as-delivered state)
3
3
(can be set via DIP switch)
3
Liquiphant FTL62
3
density setting.