False Alarm Immunity; Hazardous Location Detector Markings - Honeywell FS20X Series User Manual

Fire and flame detectors
Hide thumbs Also See for FS20X Series:
Table of Contents

Advertisement

FS20X Fire and Flame Detectors
Agency
Standard
Certificate
LPCB
EN 54-10:2002 +A1:2005 1175a/01
CPR
EN 54-10:2002 +A1:2005 2831-CPR-F0515
Additional Performance Specifications
Flame Response Sensitivity
This table provides typical response times for various fuels:
MultiBand IR plus UV Detector
Location
Fuel
Fire Size
Acetylene
12 in (0�30 m) plume - medium flame
Acetylene
10 - 12 in (0�25 - 0�30 m) plume - lazy flame
Diesel
6 in X 6 in (15�2 cm X 15�2 cm)
Ethanol
12 in X 12 in (0�3 m X 0�3 m)
Hydrogen
3/8 in dia� (9�5 mm) orifice, 32 in (0�8 m) plume
IPA
6 in X 6 in (15�2 cm X 15�2 cm)
Indoors
JP4
6 in X 6 in (15�2 cm X 15�2 cm)
JP8
6 in X 6 in (15�2 cm X 15�2 cm)
Methane
3/8 in dia� (9�5 mm) orifice, 32 in (0�8 m) plume
Methanol
12 in X 12 in (0�3 m X 0�3 m)
n-Heptane 6 in X 6 in (15�2 cm X 15�2 cm)
Silane
1/32 dia (0�8 mm) orifice, 12 in (0�3 m) plume
Acetylene
12 - 16 in (0�30 - 0�41 m) plume - large flame
Acetylene
12 in (0�30 m) plume - medium flame
Acetylene
10 - 12 in (0�25 - 0�30 m) plume - lazy flame
Diesel
12 in X 12 in (0�3 m X 0�3 m)
Ethanol
12 in X 12 in (0�3 m X 0�3 m)
Hydrogen
3/8 in dia� (9�5 mm) orifice, 32 in (0�8 m) plume
Out-
IPA
12 in X 12 in (0�3 m X 0�3 m)
doors
JP4
12 in X 12 in (0�3 m X 0�3 m)
JP8
12 in X 12 in (0�3 m X 0�3 m)
Methane
3/8 in dia� (9�5 mm) orifice, 32 in (0�8 m) plume
Methanol
12 in X 12 in (0�3 m X 0�3 m)
n-Heptane 12 in X 12 in (0�3 m X 0�3 m)
Silane
1/32 dia (0�8 mm) orifice, 12 in (0�3 m) plume
Notes
Sensitivity settings: Very
High, High, Medium
EN 54-10 Class 1
Typical
Distance
Response
(ft/m)
Time
(seconds)
35/10�7
2
40/12�2
< 2
87/26�5
< 3
50/15�2
< 3
85/25�9
< 3
87/26�5
< 3
75/22�9
< 3
87/26�5
3
70/21�3
< 3
40/12�2
< 3
87/26�5
< 3
30/9�1
< 2
100/30�5
< 3
100/30�5
< 4
90/27�4
< 3
150/45�7
4
60/18�3
< 3
75/22�9
< 3
150/45�7
< 3
150/45�7
< 4
150/45�7
< 4
60/18�3
2
40/12�2
< 2
200/61�0
< 4
50/15�2
< 3
36
FS20X Fire and Flame Detectors

False Alarm Immunity

The second column in this table shows the minimum distance at which a detector exposed to various
false fire sources did not alarm or show any signs of instability� The third column shows the sensitivity to a
one-foot square n-Heptane reference fire in the presence of those false fire sources�
False Alarm Immunity
Minimum Distance
False Fire Source
with No Alarm
Direct Sunlight
No alarm
Modulated Sunlight
No alarm
Modulated Arcwelding
9 ft 9 in (3 m)
Continuous Arcwelding
9 ft 9 in (3 m)
Resistive Electric Heater
1 ft (30�48 cm)
Flourescent Lamp
1 ft (30�48 cm)
Halogen Lamp
1 ft (30�48 cm)
Sodium Vapor Lamp
1 ft (30�48 cm)
Pelican Flashlight
1 ft (30�48 cm)
Incandescent Lamp
1 ft (30�48 cm)

Hazardous Location Detector Markings

Series 1 – North America
2 - IECEx
3 - ATEX
CLASS I DIV� 1, GRPS
ABCD
II 2 G Ex db IIC
II 2 D Ex tb IIIC
CLASS II/III, DIV� 1, GRPS
T135°C
EFG
Ex db IIC
IP66
T4 T135°C Ta = -40°C to
Ex tb IIIC T135°C
T4 Ta = -40°C to
IP66
+110°C
+110°C
T4 Ta = -40°C to +110°C
T5 Ta = -40°C to
FS20X
T5 T135°C Ta = -40°C to
T5 Ta = -40°C to +75°C
+75°C
+75°C
T6 Ta = -40°C to +60°C
T6 Ta = -40°C to
IECEx FMG14�0027X
+60°C
T6 T135°C Ta = -40°C to
FM14ATEX0058X
+60°C
CE Notified Body
IP66, NEMA Type 3, Type 4,
#: 2809
Type 4X
Sensitivity to Reference Fire
50 ft (15�24 m)
25 ft (7�62 m)
Source at 30 ft (9�14 m)
Fire at 30 ft (9�14 m)
Source at 30 ft (9�14 m)
Fire at 30 ft (9�14 m)
Source at 3 ft (91�44 cm)
Fire at 200 ft (60�96 m)
Source at 3 ft (91�44 cm)
Fire at 200 ft (60�96 m)
Source at 3 ft (91�44 cm)
Fire at 200 ft (60�96 m)
Source at 3 ft (91�44 cm)
Fire at 200 ft (60�96 m)
Source at 3 ft (91�44 cm)
Fire at 200 ft (60�96 m)
Source at 3 ft (91�44 cm)
Fire at 200 ft (60�96 m)
8 –
5 – South
7 – EU
9 – Electrical
4 – CPR
6 - Brazil
China
Korea
WEE
Rating
RoHS
ELEC (MAX): 32
1175a/01
Ex d IIC T6... T4
VDC, 150 mA
0832-CPR-
RELAY: 24 VDC, 1 A
F0515
Gb IP66
WideBand IR™/
N/A
EX tb IIIC T80 °C...
Required
For Brazil:
UV
ELET�(MAX): 32 Vcc,
T130 °C IP66
CE Notified
150 mA
Body #: 2811
RELÊ: 24 Vcc, 1A
37

Advertisement

Table of Contents
loading

Table of Contents