Parameters Of Operating Environment; Parameters Of Storage Environment - Emerson Liebert PEX User Manual

Table of Contents

Advertisement

4
Chapter 1 Overview
LSF76, LDF76, LSF85, LDF85
Note
1. The installation holes are long and flat holes. It is recommended to use M10 × 20 bolts to fix the mounting base.
2. The upper condenser must be installed on a rack during vertical installation, and the cushion pads should be installed between
the condenser and the rack for reducing vibration. It is prohibited to stack two condensers through bolt connection.

1.4.3 Parameters Of Operating Environment

Refer to Table 1-5 for parameters of operating environment.
Item
Installation position
Ambient temperature
Ambient relative humidity
Operation power
Altitude
Protection level
Note*:
Condenser fins have a corrosion resistant coating designed to provide maximum life expectancy for the heat exchanger and
protect the aluminium fins from harsh environments. The high performance coating has been tested for 2000 hours exposure to a
5% neutral salt spray test in accordance with ASTMB117 without impact to the coating
Note
When the equivalent distance between the indoor unit and the condenser exceeds 30m, refer to 5.1 Refrigerant Tubing System
in Liebert.PEX Series Air Conditioner Technical Manual for the requirement of the line equivalent length.

1.4.4 Parameters Of Storage Environment

Refer to Table 1-6 for parameters of storage environment.
Item
Storage environment
Ambient temperature
Ambient relative humidity
Storage time
Model
Table 1-5 Parameters of operating environment
The standard equivalent distance between the indoor unit and the condenser is 30m. Vertical
difference* ∆H: -5m ≤ ∆H ≤ 20m. Installation mode: horizontal or vertical mode
Outdoor temperature: -20°C ~ +45°C. Low temperature accessories are required if the temperature
is between -35°C and -20°C
Outdoor humidity: 5%RH ~ 95%RH
400V ± 10%, 50Hz
≤ 1000m. Derating is required if the altitude exceeds 1000m
Electrical control box: IP55; unit: IP20; fan motor: IP54
Table 1-6 Parameters of storage environment
Clean indoor environment with good ventilation and no dust
-40°C ~ +70°C
5%RH ~ 85%RH
The total storage time should not exceed 6 months. Otherwise, the performance needs to be
re-calibrated
Liebert.PEX Condenser User Manual
Dimension 'a'
2280
Requirement
Requirement

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents