Diagnostics and troubleshooting

22
7�4�5

Reset to factory settings

In case of unknown settings or use in a new application, it is recommended to reset the
FTR16 to its factory settings beforehand.
Factory settings:
• Process windows: 50 %
• Switching delay off
Perform factory reset
Operating magnet on "Auto Span" → green LED flashes quickly
Continue to stop operating magnet (min. 20 s):
→ after 10 s, red LED flashes slowly (warning of resetting)
→ after 20 s red LED flashes quickly
Remove operating magnet → parameter 7.4.2 to 7.4.4 reset to factory setting
7�5

Function test

• Function test only possible with parameterization mode deactivated (→ 20)!
• If the operating magnet is held ≥ 30 s against the marking, the red LED flashes and the
device automatically returns to the current switching state.
Perform function test
Operating magnet on "Auto Span", "Process Window" or "Switch Delay" (min. 2 s)
→ all LEDs light up briefly
→ current switching state is inverted
→ function test is performed
Remove operating magnet → change to normal operation
8

Commissioning

8�1

Function check

Before commissioning the measuring point, check whether the post-installation and post-
connection checks have been performed.
• "Post-installation check" checklist → 16
• "Post-connection check" checklist → 18
8�2

Powering up the measuring device

The device is ready for operation a maximum of 3 s after the supply voltage is applied.
Initial setup → 7.4.2 to 7.4.5
9
Diagnostics and troubleshooting
Error
Possible cause
Device does not
Supply voltage does not match the
respond
specification on the nameplate.
Supply voltage has the wrong
polarity.
Signal outputs do not
FTR16 not parameterized
switch
FTR16 defective
Solimotion FTR16
Remedy
Apply correct voltage.
Reverse the polarity of the supply
voltage.
Parameterize FTR16 (if necessary,
reset to factory settings beforehand).
Inspection and repair if necessary