Resetting to factory settings (reset)

By entering a certain code, you can completely or partially reset the entries for the
parameters to the factory settings
parameter (menu path: "Diagnosis" → "Enter reset code").
There are various reset codes for the device. The following table illustrates which
parameters are reset by the particular reset codes. To perform a reset, operation must
be unlocked (see the "Locking/unlocking operation" section ).→  37
Any customer-specific configuration carried out at the factory is not affected by a
reset (customer-specific configuration remains). If you want to change the customer-
specific configuration carried out at the factory, please contact Endress+Hauser
Service. As there is no separate service level, the order code and serial number can be
changed without a specific release code.
2)
Reset code
• 62 (PowerUp reset (warm start))
• The device is restarted.
• Data is read back anew from the EEPROM (process is reinitialized).
• Any simulation which may be running is ended.
• 333 (User reset)
• This code resets all the parameters apart from: device tag, linearization table,
operating hours, event logbook, current trim 4 mA , current trim 20 mA
• Any simulation which may be running is ended.
• The device is restarted.
• 7864 (Total reset)
• This code resets all the parameters apart from: operating hours, event logbook
• Any simulation which may be running is ended.
• The device is restarted.
After a "Total reset" in FieldCare you have to press the "refresh" button in order to
ensure that the measuring units are also reset.