Reset To Factory Settings; Perform Function Test - Endress+Hauser Soliwave FDR16 Brief Operating Instructions

Microwave barrier
Hide thumbs Also See for Soliwave FDR16:
Table of Contents

Advertisement

Soliwave FDR16/FQR16
Display
76

Reset to factory settings

In case of unknown settings or use in a new application, it is recommended to reset the FDR16
to its factory settings beforehand.
Perform factory reset
Operating magnet on "Auto Span" → green LED flashes quickly
Continue to stop operating magnet (min. 20 s):
→ after 10 s, red LED flashes slowly (warning of resetting)
→ after another 10 s red LED flashes quickly
Remove operating magnet → parameter reset to factory setting (7.2 ... 7.4)
Factory settings →  BA01901F
77

Perform function test

• Function test only possible with parameterization mode deactivated! → 19
• If the operating magnet is held ≥ 30 s against the marking, the red LED flashes and the
device automatically returns to the current switching state.
Perform function test
Operating magnet on "Auto Span", "Process Window" or "Switch Delay" (min. 2 s)
→ all LEDs light up briefly
→ current switching state is inverted
→ function test is performed
Remove operating magnet → change to normal operation
Endress+Hauser
Meaning
Switching delay off (factory setting)
500 ms
1 s
5 s
10 s
Commissioning
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

Soliwave fqr16