Putting The Equipment Into Operation - IBC control MiniMax Manual

Control unit for rotary heat exchanger
Hide thumbs Also See for MiniMax:
Table of Contents

Advertisement

Continued from previous page
Check that
Check that

PUTTING THE EQUIPMENT INTO OPERATION

Should be done in sequence.
Check that
Setting max speed
Setting min speed
Checking the cleaning
function
Checking the
rotation monitor
Setting the threshold
value
Finish by
the DIP switch is set for the type of signal the control equipment outputs.
See "DIP switch" setting, page 7.
the cleaning function and rotation sensor DIP switch are set to ON.
the motor rotates in the right direction in relation to the rotor's direction
of rotation.
In the event of a fault, switch two phases to the motor.
Set the "High speed" DIP switch to the ON position.
Adjust "Max rpm" so that the rotor rotates at 10-12 rpm
(or as per rotor manufacturer directions).
After a test run, set the DIP switch to OFF.
Set the "Low Speed" DIP switch in the ON position.
Adjust "Min rpm" so that the rotor rotates at 0.2-1 rpm
(or as per rotor manufacturer directions).
After a test run, set the DIP switch to OFF.
Switch off the voltage.
Make sure the cleaning DIP switch is set to ON
and the input signal is disconnected.
When power is switched on, the rotor will rotate at minimum rpm for
10 seconds.
The yellow Rotation LED will flash when the magnet passes
the magnetic sensor, regardless of DIP switch position.
Make sure the control centre is connected. Jump "Run" 5-6.
Set the minimum output signal on the control centre.
If the rotor continues to turn, increase the threshold value until it stops.
having the control unit drive the rotor at maximum and minimum
rpm and checking that the rotor speed is correct.
13