TABLE OF CONTENTS Installation Instructions Mounting Safety instructions Manufacturer´s declaration Declaration of conformity Description of functions Technical data Functions - DIP switch - Operational indications - Alarms - Settings via potentiometer - Reset Connection diagram Connections 11-12 Checks before powering up the control unit 12-13 Putting the equipment...
INSTALLATION INSTRUCTIONS The control unit must be in perfect technical condition Warning indication before use. Damage that can affect safety must be remedied immediately. Maintenance/Repairs The function of the control unit should be checked regularly. Troubleshooting and repairs may only be performed by trained personnel.
SAFETY INSTRUCTIONS The following symbols and references are used in this description. These instructions are important; they apply to personal and technical safety during operation. Safety instruction refers to instructions whose specific intent is to avoid the risk of personal injury and to prevent damage to equipment.
MANUFACTURER´S DECLARATION DECLARATION OF CONFORMITY Manufacturer IBC control AB Brännerigatan 5 A SE-263 37 Höganäs Sweden Tel: +46 42 33 00 10 Product Control unit for rotary heat exchanger Type designation MiniMax Applicable EMC Directive 2014/30/EU EU Directives Low Voltage Directive 2014/35/EU...
• When the rotor has been at a standstill for 1/2 hour, cleaning begins and the rotor turns for 10 seconds at minimum rpm. • MiniMax has an adjustable threshold of 20% of the input signal´s maximum value. • MiniMax has adjustable boost function.
TECHNICAL DATA Connection voltage 1x230-240 V +/-15% Overload 2 min/30 min 3.5 A 50/60 Hz Internal fuse **) 4 AT Power input, max. 650 W Acceleration time 0-30 s Input current, max 2.8 A Retardation time 0-30 s External fuse, max 10 A Ambient temperature, -25 - +45...
DIP SWITCH Input signal 9 10 Potentiometer 0-5 V 0-10 V 0-20 V 1-5 V 2-10 V 5-10 V 10-0 V 10-2 V 10-5 V 0-20 mA 4-20 mA Cleaning Cleaning function connected in ON function position. When the rotor has stopped for 30 minutes, the cleaning function is activated and the rotor rotates at minimum speed for 10 seconds.
OPERATIONAL INDICATIONS "Power on" is lit continuously. It flashes when the control unit has tripped. Comes on when the motor is to rotate, i.e. when the input signal exceeds the threshold value. Rotation Flashes when the magnet passes the magnetic sensor, regardless of the rotation monitor DIP switch setting.
Page 11
- Earth fault in the motor or cable ------------------------------------------------------------------------------------------------------ Overcurrent MiniMax limits thr current at 4 A and trips then after 4-5 s. Probable fault cause - The motor is too small in relation to rotor diameter - Rotor rotation sluggish - Damaged motor, e.g.
SETTINGS VIA POTENTIOMETER Boost Torque boost at low rpm. Factory set. May be increased if necessary, but motor temperature will increase. Acceleration time (0-30 s). Factory set to max; does not need adjustment. Retardation time (0-30 s). Factory set to max; does not need adjustment. Threshold value The control unit will start when the input signal exceeds the threshold value;...
Continued from previous page Alarm relay Closes between 14-15 in the event of an alarm or voltage drop-out. (13-14-15) Max 2 A resistive load / 250 V AC. Manual high speed Provides set max rpm if Run (5-6) is closed. (A1-A2) Manual low speed Provides set min rpm if Run (5-6) is closed.
Continued from previous page Check that the DIP switch is set for the type of signal the control equipment outputs. See “DIP switch” setting, page 7. Check that the cleaning function and rotation sensor DIP switch are set to ON. PUTTING THE EQUIPMENT INTO OPERATION Should be done in sequence.
EMC INSTALLATION Connection voltage 3G1.5 Rotation monitor, LiYCY 2x0.34 Not shielded Shielded Motor Input signal, LiYCY 2x0.34/0.5 Shielded Ölflex Classic 110 CY/7G0.5 Shielded EMC glands must be used for shielded cables. The above cables or equivalent must be used to comply with the EMC Directive. EMC GLAND NOTE! When connecting the shield to the EMC gland, it is important to do so as shown above.