I N T R O D U C T I O N Scope and liability This document describes the functions, the technical data of NA016 devices; instructions for mount- ing, setting and commissioning are included. This manual has been checked out, however, deviations from the description cannot be completely ruled out, so that no liability in a legal sense for correctness and completeness of the information or from any damage that might result from its use is formally disclaimed.
• Test label with following informations: data, serial number and test operator signature. Environment The NA016 device must be employed according to the environment conditions shown (see technical data). In case of different environment conditions, appropriate provisions must be provided (conditioning system, humidity control, etc...).
Page 6
MMI (Man Machine Interface) Operator front panel ThyVisor Setting and monitoring software Log file A text file that lists actions that have occurred (ThyVisor). J2SE Java Platform Standard Edition Software Firmware Upgrade Firmware upgrade eXtensible Markup Language NA016 - Manual - 05 - 2022 INTRODUCTION...
Page 7
ON delay timer with reset ( delay) OUTPUT RESET RESET INPUT ON delay timer without reset ( delay) OUTPUT INPUT DROP OFF delay timer (dropout) without reset ( delay) DROP DROP OUTPUT Symbols.ai NA016 - Manual - 05 - 2022 INTRODUCTION...
Page 8
DROP INPUT Minimum pulse width operation for output relays ( OUTPUT INPUT Latched operating mode for output relays and LEDs Latched OUTPUT INPUT Pulse operating mode for output relays OUTPUT Symbols1 .ai NA016 - Manual - 05 - 2022 INTRODUCTION...
G E N E R A L Preface The relay type NA016 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent protection can be used on feeders of any length,...
- with traditional CTs and setting I>inv ≥ 2.0 In, the measuring upper limit is 40 In - with LPCT sensors and setting I>inv = 1.0 In and In = 625 A the measuring upper limit is 12500 A NA016 - Manual - 05 - 2022 TECHNICAL DATA...
- 12500 A (primary current) for LPCT input versions, so the maximum threshold adjustment depends on the In setting (Dip switch); eg: with In = 1000 A the max setting for I>>def and I>>>def thresholds is 12500/1000 = 12.5 In NA016 - Manual - 05 - 2022 TECHNICAL DATA...
RMS value of the fundamental component for residual current Note 1 - T = number of power cycles Example, with setting T=4 the pre-trigger is 80 ms with f = 50 Hz NA016 - Manual - 05 - 2022 TECHNICAL DATA...
The circuit board additionally comprises: INPUT CIRCUITS: • Three binary input circuits, The logical input circuits and the block circuits include photo-couplers which provide for galvanic separation. OUTPUT CIRCUITS: • Four output relays (k1...K4). NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
• An eight keys 8 keyboard, • a backlight LCD display, • Eight signalling LEDs, • RS232 communication port. Note 1 The phase and residual nominal currents must be adjusted by means dip-switch. NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
This handles the menus, available both on the panel and by means of Modbus messages, which may be run from commands using the keyboard, LEDs and LCD display. MMI information is stored in EEPROM and may be loaded remotely by means of the basic protocol functions. NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Xml files used for communication. The automatic code generation criteria ensures the quality of the result in terms of the reusability, verifiability and maintainability of the software life cycle. NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Samples are processed by means DFT (Discrete Fourier Transform) algorithm and the phase and amplitude of fundamental are computed: • Phase currents I ACQUISITION ≈ IL1. a i • Residual current I ACQUISITION ≈ IE. a i NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
The CB position can be acquired by means of binary inputs connected to the auxiliary contacts: the information is used to acquire the CB position (open-closed-fault). CB position CB diagnostic Binary input allocation for CB state acquisition NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
- No-latched , in order that it stays ON for normal conditions and the other way round it goes OFF if any fault is detected and/or the auxiliary supply turns OFF. NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Trip TCS CB OPEN CB CLOSED Note 1 The LEDs 3, 4 (CB position) and 5 (TCS) are enabled only when the logger is enabled NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
IEC 60870-5-103 (Protection equipment) is available together the Modbus protocol on some version of Pro-n devices (code NA016#xCxx). Note 1 After installation, the same communication port must be selected to define the ThyVisor parameters (typically COM4, COM5,...).
CTs inputs. It must be programmed to the same value of the residual CT(s) primary nominal current. Example 1 NA016 = 100 A /1 A = 1 A Es1-IEn.ai NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Page 28
= 100 A • Measurement reading mode - With Reading Relative setting all measures are related to the nominal value, - With Reading Direct setting all measures are related to the primary value. NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Timers-F50-51.ai Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Page 30
≥ I >>> t>>> >>>RES t>> I>>>Trip relays >>>RES ≥1 I>>>Trip LEDs ≥ I >>> Trip I>>> ≥ I >>> General logic diagram of the phase overcurrent elements - 50/51 Fun_50-51S1.ai NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
52b auxiliary contact. NA016 TRIP Towards 74TCS logic Binary input INx Trip Circuit Supervision - 74TCS TCS1s.ai Note 1 The Data Logger function is available on request (to be selected on order ). NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Page 34
= R · I = R · [U / (R + R Note 1 The trip contact (TRIP) of the protection relays must be set with automatic reset (No-latched operating mode). NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
52b is the auxiliary contact in the breaker that is in the opposite position as the breaker (52b open = CB closed)). It must be assigned to the IN1 binary input. NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Note 1 The test is performed (LED) even if the concerning element is assigned to almost one output relay Note 2 The test is performed (LED & relays) even if the concerning element is assigned to almost one output relay NA016 - Manual - 05 - 2022 FUNCTION CHARACTERISTICS...
Note 4 The newest event data are stored inside the event addressed by the Last event parameter (1...100) Note 5 Counter is updated at any new record; it may be cleared by means ThyVisor NA016 - Manual - 05 - 2022 MEASURES, LOGIC STATES AND COUNTERS...
Note 1 The last change on settings ia stored inside memory addressed by the Last setting (1...10) parameter Note 2 Counter is updated at any new record; it may be cleared by means ThyVisor NA016 - Manual - 05 - 2022 MEASURES, LOGIC STATES AND COUNTERS...
= 50 Hz is 640 ms Note 1 The oscillographic recorder requires a licence; to purchase it please contact Thytronic. Note 2 COMTRADE format; (Common Format for Transient Data); This is a standard for the data exchange for various types of tests or simulation data, etc, for power system applications.
Page 40
• Value of fundamental component of phase current IL1 (IL1 Measure) • Logic state input IN1 Recording is started (triggers), with pre-trigger = 2T, I> start (General start). Phase/to/phase fault record oscillo-phase.ai NA016 - Manual - 05 - 2022 MEASURES, LOGIC STATES AND COUNTERS...
102.5 ±0.3 START TRIP N.4 fori ø 3.5 • Remove the upper tile and open the little door to access the fastening screws. Removing tie to access the fastening screws Remove-tile.ai NA016 - Manual - 05 - 2022 INSTALLATION...
Page 42
482.6 START START START START TRIP TRIP TRIP TRIP Rack mounting Rack-mount.ai To allow opening of the keyboard door a one unit space must be provided when several rack are overlapping mounted. NA016 - Manual - 05 - 2022 INSTALLATION...
Examples of connection diagrams are reported on Appendix to this manual. CAUTION Devices must be installed by qualified personnel only. No liability is accepted from Thytronic due to improper use. For the A1...A22 connections and E1...E3 (RS485), screw terminals with following characteristics are available: •...
Page 44
The use of a balance transformer with an inside diameter about twice the diameter of the the cable going through it is recommended. Fig. 2a Fig. 2b Fig. 2c Current balanced transformer Toroide.ai NA016 - Manual - 05 - 2022 INSTALLATION...
Page 45
LPCT amperometric inputs The amperometric input are designed for Low Power Current Transformer with 100 A - 22.5 mv ratio. Connections to NA016 device must be carried out by means RJ45 plugs, forming a part of the Trans- former. Note 1 The A21 and A22 terminal are link together inside the relay Nota 2 For technical data please call Thytronic.
Page 46
When no RS232 port is available on Personal Computer, a suitable USB to RS232 converter must be employed. After installation, the same communication port must be selected to define the ThyVisor parameters (typically COM4, COM5,...). NA016 - Manual - 05 - 2022 INSTALLATION...
Page 47
It is recommended to terminate the line at the extremities of the same; this must be performed on the RS485 line control unit and on the NA016 device placed at the furthest point connecting the specially provided resistor; termination can be made by means a jumper between the E1-E2 terminals.
- eliminate any potential differences between the human body and the device by touching the metallic case, - avoid touching the printed circuit and connections (tracks, component terminals), - avoid handing the device to others, - set the programming DIPs by using antistatic tools. NA016 - Manual - 05 - 2022 INSTALLATION...
Page 49
Dip-switch localization concerning the nominal current setting inside the front board Note 1 Place switches 1 ... 4 according to the number on the printed circuit board (not considering the numbers on the component) NA016 - Manual - 05 - 2022 INSTALLATION...
In = 1250 A (800 + 400 + 50) Maximum setting configurations not allowed ! Note 1 For LPCT versions the dip-switch position, located inside the CPU board, concerning the phase 1 A or 5 A current setting are irrelevant NA016 - Manual - 05 - 2022 INSTALLATION...
• All screws are tightly screwed. Note 1 The LEDs 3, 4 (CB position) and 5 (TCS) are enabled only when the logger is enabled Note 2 The “I” e “0“ keys are disabled NA016 - Manual - 05 - 2022 INSTALLATION...
SW ThyVisor The ThyVisor sw is a “browser” of data (setting, measure, etc..); it implements an engine that is afford to rebuild the menu set up and the relationships to data concerning all Thytronic protective relays by means of XML files.
“E” to be replaced by the symbol “!”. On must be remember that changes are NOT active until the Note 1 Setting changes are enabled when the La mEnabling setting by MMI parameter is set NA016 - Manual - 05 - 2022 SETTING AND COMMISSIONING...
• Test I>>> led • Test IE> led • Test IE>> led • Test I> full • Test I>> full • Test I>>> full • Test IE> full • Test IE>> full NA016 - Manual - 05 - 2022 SETTING AND COMMISSIONING...
“E” to be replaced by the symbol “!”. Differently from the Set menu the changes are stored and became active immediately without the Store command. Note 1 The tests are active only if the selected function is assigned to an output relay NA016 - Manual - 05 - 2022 SETTING AND COMMISSIONING...
K2 logic De-energized K2 mode No-latched Relays K2 tTR 200 ms None K3 logic De-energized K3 mode No-latched K3 tTR 200 ms None K4 logic De-energized K4 tTR 200 ms NA016 - Manual - 05 - 2022 SETTING AND COMMISSIONING...
Page 57
Test IE>> full > Reset counters > Reset Reset alarm > Set year 2009 Set month Set day Time Set hour Set minute 22 m Set second Set default Option Set default NA016 - Manual - 05 - 2022 SETTING AND COMMISSIONING...
Nota 3 With setting more than 2.5 In for the 50/51 elements and 0.5 IEn for the 50N/51N elements, the upper limit of the measuring range is limited to 50 In and 10 IEn respectively. NA016 - Manual - 05 - 2022 APPENDIX...
= 0.2 s t> = 0.1 s t> = 0.02 s 0.01 I /I>inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> = 700 F_51-IECA-Char.ai NA016 - Manual - 05 - 2022 APPENDIX...
= 0.1 s t> = 0.2 s t> = 0.02 s 0.01 I /I>inv 7 8 9 10 Note: match of operating and setting time takes place when I/I> = 14.5 F_51-IECB-Char.ai NA016 - Manual - 05 - 2022 APPENDIX...
= 0.1 s t> = 0.2 s t> = 0.5 s I /I >inv 0.01 7 8 9 10 Note: match of operating and setting time takes place when I/I> F_51-IECC-Char.ai NA016 - Manual - 05 - 2022 APPENDIX...
For all diagrams the output contacts are shown in de-energized state for standard reference. 50/51 50N/51N CIrcuit Breaker CB position Monitoring Trip Circuit Supervision (TCS) Three phase CTs and residual current from core balanced CT NA016-SCH.ai NA016 - Manual - 05 - 2022 APPENDIX...
Page 66
50/51 50N/51N CIrcuit Breaker CB position Monitoring Trip Circuit Supervision (TCS) Two phase CTs and residual current from core balanced CT NA016-SCH2.ai NA016 - Manual - 05 - 2022 APPENDIX...
Page 67
Connection diagram with Data Logger TRIP CIrcuit Breaker Monitoring Trip Circuit Supervision (TCS) ≅ FRONT PANEL 120Ω NA016 - Manual - 05 - 2022 APPENDIX...
50N-51N ON: Power ON and CB OPEN diagnostic OK CB CLOSED LEDs 3, 4 and 5 enabled for Logger versions only NA016#xx11 NA016#xx01 LPCT inputs - Logger LPCT inputs - No Logger NA016 - Manual - 05 - 2022 APPENDIX...
Piazza Mistral 7 - 20139 MILANO The undersigned manufacturer herewith declares that the product Protection relay - type NA016 is in conformity with the previsions of the following EC directives (including all applicable amendments) when installed in accordance with the installation instructions: Reference n°...