Amp series high-boy multiposition
oil-fired furnace (23 pages)
Summary of Contents for Dettson Chinook CC15-M-V
Page 1
HOMEOWNER: Please keep this manual near the furnace for future reference. Manufactured by: Dettson Industries Inc. Sherbrooke, Qc, Canada www.dettson.com Gas furnace manufactured on or after May 1, 2017 are not permitted to be used in Canada for heating of buildings...
a qualified technician for the installation and subsequent servicing of this furnace; 1 SAFETY 2. Do not use this furnace if any part of it was under water. Call a qualified service technician immediately to assess the damage and to replace 1.1 SAFETY LABELING AND all critical parts that were in contact with water;...
Page 5
other operations must be performed by trained service WARNING box below: personnel. When working on heating equipement, observe precautions in literature, on tags, and on labels attached to or shipped with the furnace. Other safety precautions may apply. WARNING These instructions cover minimum requirements and conform to existing national standards and safety codes.
DETECTION SYSTEMS WARNING It is recommended that carbon monoxide detectors be installed wherever oil or gas fired heaters are used. CARBON MONOXIDE POISONING HAZARD Carbon monoxide can cause bodily harm or death. Failure to follow the steps outlined below for For this reason, agency approved carbon monoxide each appliance connected to the venting system detectors should be installed in your residence and...
Table 1 – Codes and Standards TOPIC CANADA 2 INTRODUCTION Safety National Fuel Gas National Standard Code (NFGC) NFPA of Canada, Natural This multiposition Category IV condensing furnace is 54-2009/ANSI Gas and Propane CSA design certified direct vent (2 pipes) and non-direct Z223.1 Installation Code...
CAUTION FURNACE RELIABILITY HAZARD Failure to follow this caution may result in unit To optimize your HVAC experience, Dettson offers the component damage. Electrostatic discharge can Alize heat pump system. Your furnace can deliver up to affect electronic components. Take precautions...
Figure 4 – Top view CAUTION PROPERTY DAMAGE HAZARD Failure to follow this caution may result in water spillage and/or property damage. position other than upflow, multiposition pressure switch must be connected pneumatically condensate electrically to the control to allow the furnace to stop in the event of drain blockage.
position. 3. Remove the appropriate knock-out for drain trap. Refer to Figure 5 for the location of the drain trap 2. Place the drain trap gasket on the drain trap. in downflow configuration. 3. Install the drain trap and its gasket 4.
Figure 9 – Downflow condensate box pressure port Figure 11 – Downflow installation detailed 4.3 HORIZONTAL Figure 10 – Downflow installation Horizontal application is perfect for ceiling installation. Allow enough space for inclination of the furnace and drain trap. Figure 12 will help you figure orientiation, inclination and space needed.
5. Use the MULTIPOSITION DRAIN TRAP, which The pressure switch must now be electrically connected has only two ports. in series with the low fire pressure switch (top) with the brown jumper furnished in the part bag. See Figure 6 6.
Figure 14 – Horizontal installation detailed When air conditioning is used, a vapour barrier is recommended. 5 DUCT INSTALLATION Maintain a 1 in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. GENERAL REQUIREMENTS (914 mm) horizontally from the furnace.
An accessible manual equipment shut off valve MUST be SMART DUCT SYSTEM installed external to furnace casing. Dettson Industries also offers the Smart Duct System. Install a sediment trap in riser leading to furnace. Please refer to the Smart Duct Manual (X40240) for Connect a capped nipple into lower end of tee.
PROPANE CONVERSION 3. Operate the unit to the flow rate mentioned in table 4. Installer can either use test mode (see table:16) To convert from natural gas to L.P. gas, installer should or t-stat fixed rate mode. use the appropriate conversion kit, in this case B40574- 4.
as describe in table 6 below. See table 7 for configuration details. 7 ELECTRICAL CONNECTION Figure 16 – Wiring Diagram Modulating t-stat 120V WIRING Furnace must have a 120 V power supply properly connected and grounded. Proper polarity must be maintained for 120 V wiring.
ALTERNATE POWER SUPPLY erratic operation. Dettson doesn’t recommend to operate the furnace on a Contact the alternate power supply manufacturer for generator or other alternate power supply. If so it must specifications and details.
manufacturer’s installation instructions. Care must be taken to prevent the exhaust gases from one appliance 8 VENTING AND COMBUSTION from contaminating the combustion air of other gas appliances. AIR PIPING • The vent pipe and combustion air pipe must be the same diameter.
manufacturer. Follow the manufacturer’s instructions in 6. If the calculated vent length is greater than the the use of primer and cement and never use primer or maximum allowed vent length (for either vent pipe cement beyond its expiration date. or combustion air pipe), consider modifying the termination location.
6. Deburr the inside and outside of the pipe. in these codes, clearance should be in accordance with local installation codes and the requirements of the gas 7. Chamfer the outside edge of pipe for better supplier and the instructions in this manual. distribution of primer and cement.
Figure 19 – Sidewall concentric termination Figure 22 – Alternate horizontal termination A 8.9.2 Two pipe termination Maintain the required distance between vents or pairs Figure 23 – Alternate horizontal termination B of vents. Cut the required number of holes in the roof or sidewall for vent and combustion air pipes.
4. Turn the gas control knob on the «on» position. 5. Replace de burner compartement control access 9 START UP, ADJUSTMENT door. AND SAFETY CHECK WARNING TO START FURNACE Failure to replace the burner door can cause products of combustion to be released into •...
exemple, H4 followed by 3 means heating at 40% with the inducer will run for 25 seconds before the ignition trial 300 CFM. starts. • Hot-surface igniter is energized during the pre- FAULT CODE RESET purge period. To clear the fault code memory, push and hold the Fault •...
components (e.g. a condenser) on the network. This When replacing the furnace control, be sure to match L.E.D. will blink randomly any time a message is received the DIP switch settings of the original control on the by the furnace control. If no blinking is seen within replacement.
9.13.3 Heat rise adjust Installation and service must be performed by a qualified installer, service agency, or the gas supplier. This DIP switch is used to select desired temperature rise Read all instructions in this manual and retain this and all in the heating mode.
base as to provide a seal between the support 3. Leave the building immediately and the base. 4. Immediately call your gas supplier. Follow the gas • There are no obvious signs of deterioration of supplier’s instructions. the furnace. 5. If you cannot reach the gas supplier, call the fire •...
Table 17 – Fault Code CODE DESCRIPTION SOLUTION Stand-by No fault Gas Heating mode.The furnace is in heating mode. The digit displayed after in the input of the furnace. H"0" For example, H0 means the furnace is heating at 100%. H5 means the furnace is heating at approximately 50%.
Page 31
CODE DESCRIPTION SOLUTION (1) Replace high pressure control (switch). Remove bypass and restore correct operation. The high pressure control (or switch) should not be Determine reason for bypass (e.g. vent length too closed when the inducer is not running. If it is, this is a long) and correct issue.
Need help?
Do you have a question about the Chinook CC15-M-V and is the answer not in the manual?
Questions and answers