1.1.3.3.3
Locking/Unlocking the PSU Side (Cords with Twist-Lock
Mechanism)
Power Supply (System) side - Twist locking
To INSERT or REMOVE make sure the cable is UNLOCKED and push/ pull into/out of the
socket
1.1.4
Environmental Specifications
Table 1-6.
Environmental Specifications
Feature
Operating Temperature
Relative Humidity
Airflow
Heat Output
DGX A100 System
To UNLOCK the power cord, twist the
gray locking ring to the unlocked
(indicator will show an unlocked
padlock)
To LOCK the power cord, twist the
gray locking ring to the locked
position (indicator should show a
locked padlock)
Specification
¤
5
C to 30
20% to 80% non-condensing
840 CFM @ 80% fan PWM
22,179 BTU/hr
¤
¤
¤
C (41
F to 86
F)
Introduction
DU-09821-001_v06 | 6