Solar Circuit Plumbing Diagrams - All Models

The solar collectors must be the
highest point of the system. The
maximum height of the solar
installation, from the base of the
solar storage tank to the top of the
solar collectors, is 9 m. The pump
supplied will not circulate closed
circuit
fluid
through
greater than 9 m and solar gain
will not be achieved.
For heights greater than 9m, an
auxiliary pump kit (PN 299914)
must
be
installed.
'Auxiliary Pump - Solar Circuit' on
page 13 for more information. The
installation of an auxiliary pump
will enable a maximum height of
18 m to be achieved.
Maximum Total Pipe Length (solar cold + solar hot) & Number of 90° Bends
Pipe Size
DN15
Notes:
• For each additional 90° bend, reduce the maximum total pipe length by 0.5 metres.
• For each additional metre of pipe length, reduce the number of 90° bends by two.
• One 90° elbow is equal to two 90° bends.
TM024 Premier Loline Solar Drain back Service Instructions REV: A
D.O.I: 12/12/2007
This document is stored and maintained electronically by
heights
Refer
to
1 or 2 Collectors
Pipe Length
40 metres
Service. All printed copies not bearing this statement in RED are deemed "uncontrolled"
Pipe Length
90° Bends
20
30 metres
12
3 Collectors
90° Bends
20