Alarm/Warning History; Automatic Restart; Maintenancemaintenance; General Instructions - Parker Hyperchill-Plus ICEP007 User Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
set
4. Press the button "
" to see the alarm code.
5. Press the button "
" to see the next code.
esc
6. Press the button "
" to exit
4.8.1
Analog /Digital input alarms
CODICE
DESCRIZIONE
Er01
Sensor B1 cutout or broken
Er02
Sensor B2 cutout or broken
Er03
Sensor B3 cutout or broken
Er04
High pressure
Er05
Low pressure
Er06
Pump thermal cutout
Er07
Low water level
Er08
High pressure trasducer cutout or broken
Er10
Sensor B4 cutout or broken
Er12
Compressor thermal *
Er14
High temperature sensor B1
Er15
Low temperature sensor B1
Er16
High temperature sensor B2
Er17
Low temperature sensor B2
Er18
High temperature sensor B3
Er19
Low temperature sensor B3
Er20
Antifreeze
Er21
Exceeded compressor working hours
Er23
Phase monitor
Er24
Exceeded unit working hours
Er25
Communication expansion
Er26
Controller memory
!
*
(Only oil model)
If the evaporator temperature falls below 5°C for more than 120s
then an alarm "
Er12
" will occur, blocking the unit.
!
esc
Press the button "
" to reset alarms (5sec).
English

4.9 Alarm/Warning history

set
ALHi
esc
set
AZIONE
RE-
SET
Alarm
A
HySP
Alarm
A
esc
set
Alarm
A
Alarm
M
0
Alarm
M
esc
set
Alarm
M
Alarm
M
HySP
Alarm
A
Warning
M
Alarm
M
HySd
HySC
Alarm
A
esc
set
esc
Alarm
A
Alarm
A
18.06
04
Alarm
A
Alarm
A
Menu
Code
Alarm
A
HySP
Alarm number
Alarm
A
HySC
See alarm code
Warning
A
See day and month of the alarm
HySd
Alarm
M
(if the clock option is present)
Warning
A
ALHi
See hour and minutes of the alarm
HySt
(if the clock option is present)
Alarm
A
HyS1
b1 temperature at time of the alarm
Warning
A
HyS2
b2 temperature at time of the alarm
HyS3
SET conditions at time of the alarm
set
Press the button "
" to enter in the menu, using the buttons "
" select the parameter " ALHi".
"and "
set
Press the button "
" to enter in the menu, using the buttons "
"and "
" select the parameter "HySP".
set
Press the button "
" to enter in the menu, using the buttons "
"and "
" select the alarm number insert (0,1,2......39) and confi rm
set
with "
" (the number 0 is the last alarm started) .
"HySP" appears again, press "
ICEP007-024 (60Hz)
1
2
HyS1
HySt
set
set
set
esc
esc
13.46
28
DESCRIPTION
set
" to enter and see the date of the
alarm: "HySC" code (es:HP), "HySd" Date (day, month), "HySt" hour
(hour, minutes), "HyS1" "HyS2" "HyS3" sensor b1, b2 and set when the
alarm occurred.
esc
Press "
" to exit.

4.10 Automatic restart

In the event of a power failure, when power is restored the chiller will
assume the On-Off status held at the moment the power was lost.
5

MaintenanceMaintenance

a) The machine is designed and built to guarantee continuous operaa)
The machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the mainte-
nance performed.
b) When requesting assistance or spare parts, identify the machine
(model and serial number) by reading the dataplate located on the
unit.

5.1 General instructions

!
Before performing any maintenance, make sure the power to the
refrigerator is disconnected.
Y
Always use the Manufacturer's original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunction-
ing.
Y
In case of refrigerant leakage, contact qualifi ed and authorized
personnel.
Y
The Schrader valve must only be used in case of machine mal-
function: otherwise any damage caused by incorrect refrigerant charg-
ing will not be covered by the warranty.

5.2 Preventive maintenance

To guarantee lasting maximum chiller effi ciency and reliability, carry out:
Z
a)
every 6 months - clean the condenser fi ns and make sure
compressor electrical absorption is within the dataplate values;
Z
b)
kit for maintenance (par.7.5)
• kit for maintenance;
• service kit;
• individual spare parts.
7 / 8