Parker Hyperchill-Plus ICEP007 User Manual page 56

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Address Display label
App type Default
16434
dPS
USINT
16435
dPA
USINT
16478
PP2
INT
16484
t2P
INT
16440
AbrA
USINT
16437
FUA
BOOL
16388
Ud4E
BOOL
16442
dLP
USINT
16443
dLE
USINT
16475
LEDP
BOOL
16444
ddP
USINT
16418
dE1
UINT
16459
Arq
BOOL
16462
FdP
USINT
16453
S1F1
INT
16454
S2F1
INT
16455
S1F2
INT
16456
S2F2
INT
16457
S1F3
INT
16458
S2F3
INT
16463
FSMi
INT
16464
FSMA
INT
16480
ABO
BOOL
16481
DOI
USINT
9205
C1H
UINT
9206
C1HL
UINT
9207
C2H
UINT
9208
C2HL
UINT
9209
UPH
UINT
9210
UPHL
UINT
9230
H2OR
BOOL
9231
HPS1
BOOL
9232
HPS2
BOOL
9233
PMPT
BOOL
9234
HTC1
BOOL
9235
HTC2
BOOL
9236
PHAS
BOOL
9237
LH2O
BOOL
9238
ONOF
BOOL
9239
LPS1
BOOL
9240
LPS2
BOOL
9241
ALRM
BOOL
9242
UAL1
BOOL
9243
UAL2
BOOL
9244
CMP1
BOOL
9245
CMP2
BOOL
9246
FAN1
BOOL
9247
FAN2
BOOL
9248
FAN3
BOOL
9249
H2OU
BOOL
9250
PUMP
BOOL
7.3 Techincal data
Min
Max
Unit
5
0
60
Sec
5
0
60
Sec
0
0
3
30
1
72
Hours
2
0
2
FALSE(0)
FALSE(0)
TRUE(1)
FALSE(0)
FALSE(0)
TRUE(1)
2
0
10
Minutes
12
0
dPon
Sec
TRUE(1)
FALSE(0)
TRUE(1)
8
0
60
Sec
0
0
600
Sec
TRUE(1)
FALSE(0)
TRUE(1)
1
0
2
160
0
300
bar
140
0
300
bar
170
0
300
bar
150
0
300
bar
185
0
300
bar
165
0
300
bar
140
0
250
bar
185
50
300
bar
FALSE(0)
FALSE(0)
TRUE(1)
120
10
600
sec
Hours
kHours
Hours
KHours
Hours
kHours
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
ICEP007-024 (60Hz)
Read Only
Note
FALSE
Delay switching off pump (sec)
FALSE
Delay switching ON pump (sec)
FALSE
Enable dubble pump 0=single pump; 1=automatic double pump; 2=manual pump1; 3=ma-
nual pump2
FALSE
Time switch pump with PP2=1
FALSE
Start working mode of antifreeze resistor
FALSE
Antifreeze resistor
FALSE
Enable antifreeze resistor 0=disabled
FALSE
Delay low pressure alarm
FALSE
Delay water tank empy (sec)
FALSE
H2O alarm selection 0=level 1=differential
FALSE
Delay alarm water pressure switch
FALSE
Low temperature alarm delay (seconds)
FALSE
Enable control panel heater TRUE=SRQL FALSE=SRQH
FALSE
Fan disable parameter 0=No effect on fan, 1=FAN3 OFF, 2=FAN 2 and FAN3 OFF;
FALSE
Set 1 fan 1
FALSE
Set 2 fan 1
FALSE
Set 1 fan 2
FALSE
Set 2 fan 2
FALSE
Set 1 fan 3
FALSE
Set 2 fan 3
FALSE
Fan speed control minimun set At min set fan is OFF
FALSE
Fan speed control maximun set
FALSE
Abilitazione Olio
FALSE
Ritardo allarme olio (DIL6)
TRUE
Compressor 1 working hours
TRUE
Compressor 1 working hours (x1000)
TRUE
Compressor 2 working hours
TRUE
Compressor 2 working hours (x1000)
TRUE
Unit partial working hours
TRUE
Unit partial working hours (x1000)
TRUE
H2O water request
TRUE
High pressure switch 1
TRUE
High pressure switch 2
TRUE
Pump termal protection
TRUE
High temperature switch compressor 1
TRUE
High temperature switch compressor 2
TRUE
Phase monitor
TRUE
Low H2O level
TRUE
Remote On Off
TRUE
Low pressure compressor 1
TRUE
Low pressure compressor 2
TRUE
Output alarm relay
TRUE
Output valve 1
TRUE
Output valve 2
TRUE
Compressor 1 output
TRUE
Compressor 2 output
TRUE
Output FAN 1
TRUE
Output FAN 2
TRUE
Output FAN 3
TRUE
Output for H2O valve
TRUE
Output pump
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents