andrews MAXXflo EVO CWH 150/302 Installation And Maintenance Manual page 82

High effi ciency condensing stainless steel storage water heater
Hide thumbs Also See for MAXXflo EVO CWH 150/302:
Table of Contents

Advertisement

6.6 ERROR CODES (CONTINUED)
Error
Error Code Description
Code
128
Loss of fl ame during opera-
tion
130
Flue gas temperature too high Any
133
Safety time exceeded
142
Device failure (Bus)
151
BMU Internal error
152
Parameterization error
153
Unit Locked
160
Fan speed threshold not
reached
162
Air pressure switch
Maintenance
Diag.
Notes
Code
244
Count of loss-of-fl ame incidents exceeded (a maximum of 15
625
loss of fl ame incidents are permitted in a 24 hour period )
394
Flame lost in operation during safety time, before the start of the
834
modulation phase. Check the burner CO
operation and condition of the ionisation electrode.
854
Flame lost in operation within the fi rst 7 seconds after safety
time. Check the burner CO
and condition of the ionisation electrode.
253
Flame lost in modulation phase
Check causes of high temperatures before operating Appliance.
Inspect inside of heat exchanger for dirt build up. Check CO
levels at min and max output.
254
Records individual ignition failures and the times they have
395
occurred. Check gas supply, spark electrode, spark generator,
755
Ionisation probe, burner CO
245
A total of 5 unsuccessful ignition attempts has occurred within a
625
24 hour period, resulting in a permanent lockout
757
Any
Check that the appliance and OZW672 is powered and con-
nected correctly.
330
Error when closing ignition relay - Check ignition generator and
controls connections - Replace control PCB if no fault found
331
Error when opening ignition relay - Check ignition generator and
controls connections - Replace control PCB if no fault found
332
Error when closing gas valve relay - Check gas valve and con-
trols connections - Replace control PCB if no fault found
333
Error when opening gas valve relay - Check gas valve and con-
trols connections - Replace control PCB if no fault found
336
Internal safety relay error - Check if polarity of live and neu-
337
tral has been reversed to the appliance. Replace PCB if fault
repeatedly occurs.
Any
Incorrect / confl icting parameters input (last changed param-
eters need to be investigated).
622
Temperature inside the appliance casing has exceeded 90
Check heat engine door seals and door nuts are correctly
tightened. Pressing the reset for more than 10 seconds will also
produce this lockout.
848
Parameter update fi nished. Press reset to apply changes.
849
233
Fan does not reach required speed setpoint via PWM control-
749
Check wiring and operation of fan. Replace fan if necessary
377
Fan speed not reached - Home run stage
378
Fan speed not reached - Standby stage
379
Fan speed not reached - Ignition stage
380
Fan speed not reached - Pre purge stage
381
Fan speed not reached - Post purge stage
Any
Air pressure switch (APS) has activated or is open circuit. Check
fl ue restriction or incorrect fl ue installation. Check APS function
(Open circuit at 365 Pa). Check the condensate pipe system is
free to fl ow into the trap and beyond.
82
is set correctly. Check
2
is set correctly. Check operation
2
setting and fl ue system
2
MAXXfl o EVO 150/302
2
C.