ABB Relion 615 Series List Manual page 28

Motor protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 3
DNP3 protocol implementation
DNP3 device profile document
Always
When reporting event data (slave devices only)
When sending multi-fragment responses (slave devices only)
Sometimes
Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages"
Timeouts while waiting for:
Data link
None
confirm:
Complete appl.
None
fragment:
Application
None
confirm:
Complete appl.
None
response:
Others:
Select/Operate Arm Timeout, not configurable; fixed at 10s, regardless of select timeout in the HMI.
Need time interval, configurable
Unsolicited notification delay, configurable
Unsolicited response retry delay, configurable
Unsolicited offline Interval, configurable
Sends/Executes Control Operations:
WRITE binary
Never
outputs
SELECT/
Never
OPERATE
DIRECT
Never
OPERATE
DIRECT
Never
OPERATE -
NO ACK
Count > 1
Never
(Count > 1 is
accepted but
ignored)
Pulse on
Never
Pulse off
Never
Latch on
Never
Latch off
Never
Queue
Never
Clear queue
Never
The circuit breaker control model is configurable for either direct or SBO mode in the circuit breaker settings. If the operation mode does not
match the CROB, the returned CROB status is hardware error (4). All other control points may be controlled by either direct or SBO controls.
Reports binary input change events when no specific variation
requested:
Never
Table continues on next page
22
Fixed at ____
Fixed at ____
Fixed at ____
Fixed at ____
Always
Always
Always
Always
Always
Always
Always
Always
Always
Always
Always
Reports time-tagged binary input change events when no specific
variation requested:
Variable
Configurable
Variable
Configurable
Variable
Configurable
Variable
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Sometimes
Configurable
Never
1MAC254287-MB A
REM615 ANSI
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rem615 ansi