ABB Relion 615 Series List Manual page 16

Motor protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 2
DNP3 data mappings
No
61850 Path
event
LD0.LEDPTRC1.Str.phsB
LD0.LEDPTRC1.Str.phsC
LD0.TRPPTRC1.Tr.general
LD0.TRPPTRC1.Op.general
LD0.TRPPTRC2.Tr.general
LD0.TRPPTRC2.Op.general
*
LD0.SSCBR1.InSprChStr.stVal
*
LD0.SSCBR1.InSprCha.stVal
*
LD0.SSCBR1.InPresAlm.stVal
*
LD0.SSCBR1.InPresLO.stVal
*
LD0.SSCBR1.InPosOpn.stVal
*
LD0.SSCBR1.InPosCls.stVal
LD0.SSCBR1.OpnAlm.stVal
LD0.SSCBR1.ClsAlm.stVal
LD0.SSCBR1.SprChaAlm.stVal
LD0.SSCBR1.OpNumAlm.stVal
LD0.SSCBR1.OpNumLO.stVal
LD0.SSCBR1.LonTmAlm.stVal
LD0.SSCBR1.PresAlm.stVal
LD0.SSCBR1.PresLO.stVal
*
LD0.SSCBR1.PosOpn.stVal
*
LD0.SSCBR1.PosIvd.stVal
*
LD0.SSCBR1.PosCls.stVal
LD0.SSCBR1.APwrAlm.stVal
LD0.SSCBR1.APwrLO.stVal
LD0.SSCBR1.CBLifAlm.stVal
LD0.EFLPTOC1.Str.general
LD0.EFLPTOC1.Op.general
*
LD0.EFLPTOC1.InEnaMult.stVal
LD0.DEFLPTOC1.Str.general
LD0.DEFLPTOC1.Op.general
LD0.XGGIO130.Ind1.stVal
LD0.XGGIO130.Ind2.stVal
LD0.XGGIO130.Ind3.stVal
Table continues on next page
10
Default
Default
Disabled Description
Index
Class
11
0,1
12
0,1
13
0,1
14
0,1
15
0,1
16
0,1
17
0
18
0
19
0
20
0
21
0
22
0
23
0,1
24
0,1
25
0,1
26
0,1
27
0,1
28
0,1
29
0,1
30
0,1
31
0
32
0
33
0
34
0,1
35
0,1
36
0,1
86
0,1
87
0,1
88
0
105
0,1
106
0,1
111
0,1
112
0,1
113
0,1
Global conditioning Start
Global conditioning Start
TRPPTRC1 General trip output signal
TRPPTRC1 Operate input signal
TRPPTRC2 General trip output signal
TRPPTRC2 Operate input signal
SSCBR1 CB spring charging started input
SSCBR1 CB spring charged input
SSCBR1 Binary pressure input for alarm
SSCBR1 Binary pressure input for lockout indication
SSCBR1 POSOPEN
SSCBR1 POSCLOSE
SSCBR1 CB open travel time exceeded set value
SSCBR1 CB close travel time exceeded set value
SSCBR1 Spring charging time has crossed the set value
SSCBR1 Number of CB operations exceeds alarm limit
SSCBR1 Number of CB operations exceeds lockout limit
SSCBR1 CB 'not operated for long time' alarm
SSCBR1 Pressure below alarm level
SSCBR1 Pressure below lockout level
SSCBR1 CB position is open
SSCBR1 INVALIDPOS
SSCBR1 CB position is closed
SSCBR1 Accumulated currents power (Iyt) exceeded
alarm limit
SSCBR1 Accumulated currents power (Iyt) exceeded
lockout limit
SSCBR1 Remaining life of CB exceeded alarm limit
EFLPTOC1 Start
EFLPTOC1 Operate
EFLPTOC1 Enable current multiplier
DEFLPDEF1 Start
DEFLPDEF1 Operate
X130 (BIO) X130-Input 1
X130 (BIO) X130-Input 2
X130 (BIO) X130-Input 3
1MAC254287-MB A
REM615 ANSI
Point List Manual