Download Print this page

Introduction; Description Of Operation; Receiving & Storage; Installation - Vag GA Industries FIGURE 927 Installation, Operation And Maintenance Manual

High capacity air release valves for sewage & wastewater

Advertisement

INSTALLATION, OPERATION and
Figure 927 Sewage Air Release Valves

INTRODUCTION

This manual will provide the information to
properly install, operate and maintain the valve
to ensure a long service life.
Valve is ruggedly constructed to provide years of
trouble-free
operation
maintenance.
CAUTION
The valve is NOT recommended for use with
toxic fluids, fuels or fluids containing hazardous
gases
CAUTION
The valve will not function if used at a pressure
higher than the maximum working pressure
indicated on the nameplate.
The Shop Order (SO) Number, Figure Number,
size and pressure rating are stamped on a
nameplate attached to the valve. Please refer to
the SO number when ordering parts.

DESCRIPTION OF OPERATION

The Figure 927 Air Release Valve is designed to
automatically vent air and sewage gas that has
accumulated within the valve. These valves are
usually installed at high points in the system
where air tends to collect. The valve as shipped
is "normally open" and will vent air through its
orifice at the top of the valve. The float rises
when water enters the valve and closes the
orifice. Air from the system accumulates in the
valve forcing the water level down until the float
drops and opens the venting orifice. As air is
released the water level rises lifting the float and
re-closing the valve.
This sequence occurs as often as necessary to
release air that has collected in the valve.
RECEIVING AND STORAGE
Inspect the valve upon receipt for damage
during shipment. Carefully unload all valves to
the ground without dropping.
MAINTENANCE
The Air Release
with
minimal
2
The valves should remain in a clean, dry and
weather protected area until installed. For long
term storage (greater than 6 months) the rubber
surfaces of the seat should be coated with a
non-toxic lubricant such as "SuperLube" made
by Synco Chemical. Do not expose the rubber
parts to sunlight or ozone.

INSTALLATION

The Figure 927 is standard with 2" or 3" NPT
screwed
connections,
connections can be provided on special order.
The 4" is standard with a flanged connection.
Consult the drawings of record to verify the
configuration supplied and installed.
The valve must be installed in an upright vertical
orientation, normally at a high point in the
system.
If installed outdoors, below ground in a vault or
in an unheated area, adequate freeze protection
must be provided.
An isolating valve should be installed between
the valve and the pipeline or system to facilitate
maintenance
(included
attachments).
Carefully screw threaded end valves onto pipe
nipple using compatible thread sealant. Tighten
valve using wrench flats.
TIGHTEN.
Flat-faced flanged valves should be mated with
flat-faced flanges and full-face gaskets. If ring
gaskets are used the bolt material shall be
ASTM A307 Grade B (or equivalent).
strength bolting should only be used with full-
face gaskets.
Lower heavy valves over the mating flange
using slings or chains around the valve body.
Lubricate the bolts or studs and insert around
flange.
Lightly tighten bolts until gaps are
flanged
pipeline
with
backflushing
DO NOT OVER-
Higher

Advertisement

loading