Huawei FusionModule500 Smart User Manual page 66

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Check Item
Equipment room
height
Equipment room
area
Equipment room
maintenance
clearance
Power system
Water port
Figure 4-1 Space requirements
If any of the requirements is not met, contact Huawei technical support.
Issue 02 (2021-06-30)
Specifications
≥ 2.6 m
≥ 10.15 m
At least 1200 mm, 1000 mm,
and 1000 mm maintenance
clearance should be reserved
from the front door, rear, and
side of the cabinet, respectively.
At least 100 mm clearance
should be reserved from the
wall.
208–240 V 1Ph 50 Hz/60 Hz
Condensate drain outlet: Drains
condensate water from the
smart cooling product.
NO TE
Copyright © Huawei Technologies Co., Ltd.
2
4 Installation Guide
Check Result
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
□ Passed □ Failed
57