Huawei FusionModule500 Smart User Manual page 166

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Maintenance
Area
Issue 02 (2021-06-30)
Maintenance
Operation
Item
Battery bolts
-
Cables between
-
batteries
Battery voltage
-
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Troubleshootin
g
The location of
Take photos
the signs marked
from multiple
on battery
angles and
terminal bolts
contact Huawei
indicating tight
technical
connections does
support.
not change.
No cable
Replace the
deteriorates and
faulty cable.
the insulation
layer does not
crack.
● Equalized
1. Check
charging
voltage: 53.5
V DC
● Float
charging
voltage: 53.4
V DC
2. If the
3. If the fault
6 O&M
whether the
equalized
charging
voltage and
float
charging
voltage of a
battery are
normal.
charging
voltage of a
battery
exceeds the
specifications
requirement,
perform a
complete
forcible
equalized
charging for
the battery,
and check
again
whether the
voltage is
normal.
persists,
contact
Huawei
technical
support.
157