Huawei FusionModule500 Smart User Manual page 162

Mini data center
Hide thumbs Also See for FusionModule500 Smart:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual (Philippines, FusionModule500-
SU61A12S)
Maintenance
Area
Intelligent lithium
battery
monitoring system
Water sensor and
water detection
cable
Issue 02 (2021-06-30)
Maintenance
Operation
Item
Battery
-
management
alarm
Cleanliness
-
Battery
-
connection
Measurement of
-
the ambient
temperature of
the intelligent
battery
monitoring system
Functions of the
Place the water
water sensor and
detection cable
water detection
into the water
cable
and check
whether a water
leakage alarm is
generated by the
water sensor.
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Troubleshootin
g
No battery
Identify the
management
cause of an
alarm is
alarm based on
generated.
the alarm
information.
Wipe the battery
Remove dust.
surface using a
piece of white
paper and the
paper does not
turn black.
Battery terminals
Locate poor
and cables are in
contact points
good contact.
between battery
terminals and
cables.
The ambient
Locate the
temperature of
cause of an
the intelligent
abnormal
battery
temperature.
monitoring
system is lower
than 45°C.
A water leakage
If a water
alarm is
leakage alarm is
generated.
not generated,
replace the
water detection
cable.
6 O&M