Transporting The Device; Mounting - Endress+Hauser Liquiphant FTL64 Operating Instructions Manual

Point level switch for liquids in high-temperature applications
Hide thumbs Also See for Liquiphant FTL64:
Table of Contents

Advertisement

Mounting

10
Storage temperature
–40 to +80 °C (–40 to +176 °F)
Optional: –50 °C (–58 °F), –60 °C (–76 °F)
4.3.2

Transporting the device

• Transport the device to the measuring point in the original packaging
• Hold the device by the housing, temperature spacer, flange or extension pipe
Take suitable measures to protect the coating!
• Do not bend, shorten or extend the tuning fork
 2
Handling the device during transportation
5
Mounting
WARNING
L
Loss of protection rating if the device is opened in a wet environment.
Only open the device in a dry environment!
Mounting instructions
• Any orientation for device with short pipe up to approx. 500 mm (19.7 in)
• Vertical orientation from above for device with long pipe
• Minimum distance between the fork tip and the tank wall or pipe wall: 10 mm (0.39 in)
Liquiphant FTL64