SySTEM STARTUP
Available for Installers Only
Hold MENU Button: <Settings>/<System Startup>
• This menu can be accessed on the first power up or from the default
screen by holding down the Menu button for five seconds.
• When powered, the SMC performs a self diagnostics-test.
• On the first power up, the System Startup screen will appear after
the initialization is complete. If it doesn't, the SMC has already been
configured.
• The System Startup menu sets the main operating modes that apply to
the application. These settings must be set by the installer.
PROGRAM SWITCh SETTING
To be able to change the SMC settings the Program/Run Switch must be
set to Program. The switch is located under the Enclosure Wiring Cover
for security.
SENSOR TyPE
Slab, Outdoor
Hold MENU Button: <Settings>/<System Startup>/..../Sensor Type
• If Slab is selected, the SMC shall use the Slab sensor logic and
measure the slab temperature and detect precipitation. See "Slab
Sensor Operation Overview" on page 4.
• If Outdoor is selected, the SMC shall use the Outdoor temperature as
the snow melting guide. See "Outdoor Sensor Operation Overview"
on page 6.
CONTROL MODE
Motorized Valve, Boiler, Ext. Interface
Hold MENU Button: <Settings>/<System Startup>/..../Sensor Type/Control Mode
• The SMC offers three different methods to control the slab heating. See
"Typical Snowmelt Piping Configuration" on page 8.
• The Motorized Valve option controls a floating or modulating (0-10V or
4-20mA) motorized valve. The valve can be a 3-way on the slab loop or
a 2-way controlling steam to a shell-and-tube heat-exchanger.
• The Boiler option operates a 4-20mA or a 0-10V modulating boiler. This
option targets installations using condensing boilers.
• The Ext. Interface option sends a 4-20mA signal as a slab target
temperature to a multi-boiler control (Multi-MOD Platinum, Mini-MOD,
or equivalent). This option will enable the 4mA and 20mA temperature
setting menu.
EXTERNAL INPUT
Shutdown, Enable
Hold MENU Button: <Settings>/<System Startup>/..../Control Mode/ External Input
• This menu determines the function of terminals 32 and 33. See "Wiring
the Shutdown / Enable" on page 17.
22
Default: Slab
Default: Motorized Valve
Default: Shutdown
SMC Installation and Operation Manual
------ SETTINGS ------
Season
Winter
Warm W.Cutoff
Idle Set Point 34 F
Heating Curve
<System Settings>
<Maintenance>
<System Startup>
▲
▼
BACK
SELECT
PROGRAM
--- SENSoR TYPE ---
Slab
outdoor
▲
▼
BACK
-- CoNTRoL ModE --
Motorized Valve
Boiler
Ext.Interface
▲
▼
BACK
--- EXTERNAL INPUT ---
Shutdown
Enable
▲
▼
BACK
38 F
+0
DO NOT
RUN
SAVE
SAVE
SAVE