11. M-NET CONTROL
11-4-3. System examples
Factory setting
Original switch setting of the outdoors, indoors, controllers, LM-AP, and BM ADAPTER at shipment is as follows.
Outdoor unit
Indoor unit
ME remote controller
LM-AP
BM ADAPTER
Setting at the site
DipSW5-1 (Outdoor)
DipSW1-2 (LM-AP)
CN40/CN41
11-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller
<Three outdoor units>
PUHY
OC
OS1
00
00
CN40
CN41
CN40
CN41
DipSW5-1
DipSW5-1
OFF
OFF
TB3
TB3
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. No address setting is needed.
3. For a system having more than 32 indoor unit, confirm the need of Booster at 11-3. "System configuration restrictions".
4. When a PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
MEES21K108
: Address: 00, CN41: ON (Jumper), DipSW5-1: OFF
: Address: 00
: Address: 101
: Address: 247, CN41: ON (Jumper), DipSW1-2: OFF
: Address: 000, CN41: ON (Jumper)
: When the System Controller is used, all the Dip SW5-1 at the outdoor units should be
set to "ON". * Dip SW5-1 remains OFF when only LM-AP is used.
: When the LM-AP is used together with System Controller, DipSW1-2 at the LM-AP should be
set to "ON".
: Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Change jumper from CN41 to CN 40 at LM-AP will activate transmission power supply to LM-AP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole system controller system.
<Two outdoor units>
PUHY
OS2
OC
00
00
CN40
CN41
CN40
CN41
DipSW5-1
DipSW5-1
OFF
OFF
TB3
TB3
TB3
Group 1
Indoor unit
00
TB5
TB15
TB5
*1
SRU
*1
Wireless R/C
<One outdoor unit>
PUHY
OS1
OC
00
00
CN40
CN41
CN40
CN41
DipSW5-1
DipSW5-1
OFF
OFF
TB3
Group 2
00
00
TB15
TB5
TB15
MA R/C
Hyper Heating Inverter Y-Series
Group 3
Group 4
00
00
TB5
TB15
TB5
TB15
MA R/C
MA R/C
(Main)
MA R/C
(Sub)
87