Mitsubishi Electric CITY MULTI PUHY-HP72-240TNU-A Data Book page 14

Hide thumbs Also See for CITY MULTI PUHY-HP72-240TNU-A:
Table of Contents

Advertisement

1. SPECIFICATIONS
Outdoor Model
Indoor Model
Power source
Cooling capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
cooling
Outdoor
Heating capacity
(Nominal)
Power input
(460) Current input
(Rated)
Power input
(460) Current input
Temp. range of
Indoor
heating
Outdoor
Indoor unit
Total capacity
connectable
Model/Quantity
Sound pressure level (measured in anechoic room) *3
Sound power level (measured in anechoic room) *3
Refrigerant
Liquid pipe
piping diameter
Gas pipe
Set Model
Model
Minimum Circuit Ampacity
Maximum Overcurrent Protection
FAN
Type x Quantity
Airflow rate
Control, Driving mechanism
Motor output
*4 External static press.
Compressor
Type x Quantity
Manufacture
Starting method
Motor output
Case heater
Lubricant
External finish
External dimension H x W x D
Protection
High pressure protection
devices
Inverter circuit (COMP./FAN)
Fan motor
Refrigerant
Type x original charge
Control
Net weight
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Pipe between unit and
Liquid pipe
distributor
Gas pipe
Defrosting method
Drawing
External
Wiring
Standard
Document
attachment
Accessory
Optional parts
Remarks
Notes:
1.Cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 80°FD.B./67°FW.B. (26.7°CD.B./19.4°CW.B.), Outdoor: 95°FD.B. (35°CD.B.)
2.Heating conditions (Test conditions are based on AHRI 1230)
Indoor: 70°FD.B. (21.1°CD.B.), Outdoor: 47°FD.B./43°FW.B. (8.3°CD.B./6.1°CW.B.)
3.Cooling mode/Heating mode
4.External static pressure option is available (0.12 in.WG, 0.24 in.WG, 0.32 in.WG/30 Pa, 60 Pa, 80 Pa).
* Due to continuing improvement, above specifications may be subject to change without notice.
MEES21K108
Non-Ducted
*1 BTU/h
kW
kW
A
BTU/h
kW
kW
A
W.B.
D.B.
*2 BTU/h
kW
kW
A
BTU/h
kW
kW
A
D.B.
W.B.
dB <A>
dB <A>
in. (mm)
in. (mm)
PUHY-HP96YNU-A
A
A
Propeller fan x 2
cfm
3
m
/min
L/s
Inverter-control, Brushless DC motor
kW
0.46+0.46
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1
MITSUBISHI ELECTRIC
Inverter
kW
4.5 x 1
kW
MEL46
Pre-coated galvanized steel sheet
<MUNSELL 3Y 7.8/1.1 or similar>
in.
71-5/8 x 49-1/4 x 29-3/8
mm
1,818 x 1,250 x 745
High pressure sensor, High pressure switch at 4.15 MPa
(601 psi)
Over-current protection
R410A x 23 lbs + 12 oz (10.8 kg)
lbs (kg)
688 (312)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
in. (mm)
3/8 (9.52) Brazed
in. (mm)
7/8 (22.2) Brazed
KE94G817
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
PUHY-HP192YSNU-A
3-phase 3-wire 460 V ±10% 60 Hz
192,000
56.3
13.79
19.2
184,000
53.9
12.58
17.5
59~75°F (15~24°C)
23~126°F (-5~52°C)
215,000
63.0
15.91
22.1
206,000
60.4
14.39
20.0
59~81°F (15~27°C)
-22~60°F (-30~15.5°C)
50~130% of outdoor unit capacity
P04~P96/1~48
59.5/62.0
78.5/81.0
5/8 (15.88) Brazed
1-1/8 (28.58) Brazed
20
30
7,400
210
3,500
-
High pressure sensor, High pressure switch at 4.15 MPa
-
LEV and HIC circuit
Auto-defrost mode (Reversed refrigerant cycle)
KB94C0GQ
Installation Manual
Details refer to External Drw
Outdoor Twinning kit: CMY-Y100CBK3
joint: CMY-Y102SS/102LS-G2, CMY-Y202S/302S-G2
Header: CMY-Y104/108/1010C-G
Hyper Heating Inverter Y-Series
Ducted
12.94
18.0
15.06
21.0
PUHY-HP96YNU-A
20
30
Propeller fan x 2
7,400
210
3,500
Inverter-control, Brushless DC motor
0.46+0.46
0 in.WG (0 Pa)
Inverter scroll hermetic compressor x 1
MITSUBISHI ELECTRIC
Inverter
4.5 x 1
-
MEL46
Pre-coated galvanized steel sheet
<MUNSELL 3Y 7.8/1.1 or similar>
71-5/8 x 49-1/4 x 29-3/8
1,818 x 1,250 x 745
(601 psi)
Over-current protection
-
R410A x 23 lbs + 12 oz (10.8 kg)
688 (312)
Salt-resistant cross fin & copper tube
Copper pipe, tube-in-tube structure
3/8 (9.52) Brazed
7/8 (22.2) Brazed
KE94G817
Unit converter
BTU/h
=kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.