Mitsubishi Electric CITY MULTI PUHY-HP72-240TNU-A Data Book page 80

Hide thumbs Also See for CITY MULTI PUHY-HP72-240TNU-A:
Table of Contents

Advertisement

10. ELECTRICAL WORK
The local standards and/or regulations is applicable at a higher priority.
10-4-2. PUHY-HP144, 192, 240TSNU/YSNU
<In the case a system controller is connected.>
Note12
SC
Connector
OU
CN41 CN40
Note4
TB1
TB3
Breakers for
current leakage Switch
(L1,L2,L3)
(M1,M2)
Power supply
3-phase 3-wire
208-230 60Hz(TSNU)
460V 60Hz(YSNU)
Note11,13
G
Note3
To *1 or *2
(Using MA remote controller)
Connecting TB5 terminal.
Breakers for
current leakage Switch
Power supply
1-phase
208-230 60Hz
Note11
* Power supply
specifications vary with
the model of connected
indoor units
Indoor-outdoor
transmission cable
2
>=1.25mm
Shield cable
(Using ME remote controller)
Connecting TB5 terminal.
Breakers for
current leakage Switch
Power supply
1-phase
208-230 60Hz
Note11
* Power supply
specifications vary with
the model of connected
indoor units
Indoor-outdoor
transmission cable
2
>=1.25mm
Shield cable
Symbol
OU
Outdoor unit
IU
Indoor unit
SC
System controller
MA R/C
MA remote controller
ME R/C
ME remote controller
MEES21K108
Central control
transmission cable
2
>=1.25mm
Shield cable
(CVVS, CPEVS
MVVS)
Note4
To other OU
(L1,L2,L3)
TB7
Breakers for
(M1,M2)
current leakage Switch
Power supply
3-phase 3-wire
TB7
208-230 60Hz(TSNU)
(S)
460V 60Hz(YSNU)
Note11,13
*1
TB2
TB2
TB5
TB15
TB5
TB15
(L,N)
(L,N)
(M1,M2)
(1,2)
(M1,M2)
(1,2)
S
S
IU
(Shield)
(Shield)
MA R/C
MA R/C
*2
TB2
TB2
TB5
TB15
TB5
TB15
(L,N)
(L,N)
(M1,M2)
(1,2)
(M1,M2)
(1,2)
S
S
IU
(Shield)
(Shield)
Note7
Note8
ME R/C
ME R/C
Minimum Wire thickness
Model
Power wire
2
[mm
(AWG)]
208V
230V
PUHY-HP72TNU
21.2 (4)
13.3 (6)
PUHY-HP96TNU
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
PUHY-HP120TNU
PUHY-HP72YNU
5.3 (10)
PUHY-HP96YNU
5.3 (10)
8.4 (8)
PUHY-HP120YNU
Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol
3 The shield wire of transmission cable should be connected to the grounding terminal at
Outdoor unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected
together.
The broken line at the scheme means shield wire.
4 The connector change from CN41 to CN40 at one of the outdoor units will enable the
outdoor unit to supply power to TB7 . The transmission cable (above 1.25mm
OU
CVVS/CPEVS/MVVS) among Outdoor units and system controllers is called central
control transmission cable. The shield wire of the central control transmission cable must
be grounded at the Outdoor unit whose CN41 is changed to CN40. When the power
supply unit PAC-SC51KUA is used, connect the shielded cable to the ground terminal on
the PAC-SC51KUA.
5 MA R/C transmission cable (0.3-1.25mm
TB1
R/C transmission cable (0.3-1.25mm
cable to the ME R/C can be extend using a M-NET cable (>=1.25mm
TB3
TB7
is counted in the M-Net length.
(M1,M2)
(M1,M2)
6 To wire PAR-CT01MAU, PAR-40MAAU, and PAC-YT53CRAU, use a wire with a diameter
of 0.3mm
TB7
7 MA remote controller and ME remote controller should not be grouped together.
(S)
When a PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA
remote controllers can be connected to the same group.
8 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
G
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
"Grouping".
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
Note3
address to Indoor unit and ME remote controller. For the method, refer to 11-4. "Address
setting".
9 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 11-3. "System configuration restrictions".
10 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
11 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Outdoor unit(s) or Indoor unit(s).
12 When System controller (SC) is connected to the system, turn the SW5-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.
Pull box
Note8
Breakers for
current leakage Switch
Power supply
1-phase
TB2
TB5
TB15
208-230 60Hz
(L,N)
(M1,M2)
(1,2)
S
(Shield)
Note7
Note8
Pull box
Note8
Breakers for
current leakage Switch
Power supply
TB2
1-phase
TB5
TB15
(L,N)
208-230 60Hz
(M1,M2)
(1,2)
S
(Shield)
(Shield)
G wire
2
[mm
(AWG)]
208V
230V
21.2 (4)
13.3 (6)
60A 100mA 0.1sec. or less
21.2 (4)
21.2 (4)
70A 100mA 0.1sec. or less
21.2 (4)
21.2 (4)
70A 100mA 0.1sec. or less
460V
5.3 (10)
5.3 (10)
8.4 (8)
Hyper Heating Inverter Y-Series
means a screw terminal for wiring.
2
) must be less than 200m in length, while ME
2
) must be less than 10m in length. But transmission
2
[AWG 22].
TB2
TB5
TB15
(L,N)
(M1,M2)
(1,2)
TB1
G
S
(R,S)
E
(Shield)
TB2 TB3
MA R/C cable
S
S
0.3-1.25mm
(Shield)
(Shield)
<=200m
Note5
Transmission
booster
Note9
Note10
MA R/C
TB2
TB5
TB15
(L,N)
(M1,M2)
(1,2)
TB1
G
S
(R,S)
E
(Shield)
TB2 TB3
ME R/C cable
S
S
(Shield)
0.3~1.25mm
<=10m
Note5
Transmission
booster
Note9
Note10
ME R/C
Breaker for current leakage
208V
230V
50A 100mA 0.1sec. or less
60A 100mA 0.1sec. or less
60A 100mA 0.1sec. or less
460V
25A 30mA or 100mA 0.1sec. or less
30A 30mA or 100mA 0.1sec. or less
35A 30mA or 100mA 0.1sec. or less
2
, shielded,
2
) when the length
2
2
78

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents