5. SOUND LEVELS

5-1. Sound levels in cooling mode

5. SOUND LEVELS
Measurement condition
PUHY-HP72, 96, 120TNU/YNU
Sound level of PUHY-HP72T(Y)NU-A
90
Cool
Low
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
Standard Cooling
60Hz
54.0 58.0 57.5 54.5 48.0 43.5
Low noise mode
60Hz
50.5 47.0 40.0 39.5 34.0 27.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Sound level of PUHY-HP96T(Y)NU-A
90
Cool
Low
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
Standard Cooling
60Hz
61.0 58.5 58.0 55.0 50.0 44.5
Low noise mode
60Hz
60.5 56.5 47.5 28.5 26.5 23.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Depending on the operation conditions, the unit generates noise caused by valve actuation, refrigerant flow, and
pressure changes when operating normally. Please consider to avoid location where quietness is required.
MEES21K108
1m
Measurement
location
60Hz
60Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
250
500
1k
2k
4k
8k
dB(A)
39.0
35.5
55.0
25.5
30.5
40.5
60Hz
60Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
250
500
1k
2k
4k
8k
dB(A)
40.0
35.5
56.0
12.5
14.0
43.5
Sound level of PUHY-HP120T(Y)NU-A
90
60Hz
Cool
Low
60Hz
80
70
60
50
40
30
Approximate minimum
20
audible limit on
continuous noise
10
63
125
250
500
Octave band central frequency (Hz)
63
125
250
Standard Cooling
60Hz
68.5 61.0 62.0 58.5 53.0 48.5
Low noise mode
60Hz
68.0 56.0 44.5 32.5 30.5 27.5
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
Hyper Heating Inverter Y-Series
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
1k
2k
4k
8k
500
1k
2k
4k
8k
dB(A)
43.0
36.0
59.5
18.0
18.0
45.0
23